6-2-2  Installation direction and clearance 
 
Wire each unit in consideration of the maintainability and the heat dissipation, also secure sufficient 
space for ventilation. 
 
(1) Installation 
clearance 
 
60mm 
or more 
75mm 
or more
1mm or more 
100mm 
or more 
10mm 
or more 
100mm 
or more 
80mm
or more
Inlet 
Filter 
Exhaust
Exhaust
10mm 
or more 
100mm 
or more 
100mm 
or more 
60mm 
or more 
260m
60mm 
60mm 
 
 
 
CAUTION
 
1.  The operation ambient temperature for the drive unit is 55ºC or less. 
2.  Because heat can easily accumulate in the upper portion of the units, give 
sufficient consideration to heat dissipation when designing the panel. If 
required, install a fan in the panel to agitate the heat in the upper portion of 
the units. 
 
 
(2)  Panel structure of the unit back face 
The type "(a)" that has substantial cooling effect is recommended. 
 
 
Filter 
(a) Back face inlet type 
Cooling will be more high- 
efficiency by installing a partition 
plate inside to separate inlet and 
exhaust. 
Fan inlet hole 
(b) Side face inlet type 
Filter
Install a partition plate inside 
to separate inlet and exhaust. 
Fan inlet hole