2.  Start up and Adjustment Procedure 
2.2  Setting of Various Switches 
 
 
 
III-6 
 
2)  Remote I/O unit setting switches 
 
 
There is a lever-type switch (DS1) and rotary switch (CS1) in the center from of the remote I/O unit. 
  
The 
DX10
† model has one of each switch, and DX11†/12†/14† has two of each switch. 
 
 
All DS1 levers must be set and fixed to "OFF: left side". The CS1 setting is "0" to "7", and should be set 
while referring to the following table. However, the PCB output (DO) on the right side of 
DX11
†/12†/14† looking from the front is a 16-point PCB, so take care. 
 
 
Make sure that the CS1 setting No., is different from other CS1 setting Nos. 
 
 
 
Remote I/O unit CS1 setting 
Read in device No. 
Output device No. 
On both units 
Left side of unit 
Right side of unit 
Rotary switch 
CS1 No. 
1st 
system 
2nd 
system 
1st 
system 
2nd 
system 
1st 
system 
2nd 
system 
0 X00~X1F 
I00~I1F 
Y00~Y1F
J00~J1F
Y00~Y0F 
J00~J0F
1 X20~X3F 
I20~I3F 
Y20~Y3F
J20~J3F
Y20~Y2F 
J20~J2F
2 X40~X5F 
I40~I5F 
Y40~Y5F
J40~J5F
Y40~Y4F 
J40~J4F
3 X60~X7F 
I60~I7F 
Y60~Y7F
J60~J7F
Y60~Y8F 
J60~J6F
4 X80~X9F 
I80~I9F 
Y80~Y9F
J80~J9F
Y80~Y8F 
J80~J8F
5 XA0~XBF 
IA0~IBF 
YA0~YBF
JA0~JBF
YA0~YAF 
JA0~JAF
6 XC0~XDF 
IC0~IDF 
YC0~YDF
JC0~JDF
YC0~YCF JC0~JCF
7 XE0~XFF 
IE0~IFF 
YE0~YFF
JE0~JFF
YE0~YEF 
JE0~JEF
 
 
 
 
Left input 
connector
 
DIO 
specification 
switch (DS1) 
Rotary  
switch (CS1)
 
Left output 
connector
 
DX10
†
Front view
Front view 
Left input 
connector 
DIO 
specification 
switch (DS1) 
Rotary 
switch (CS1) 
Left output 
connector 
Left input 
connector 
DIO 
specification 
switch (DS1) 
Rotary 
switch (CS1)
Left output 
connector 
Front view 
Outline drawing 
DX11
†/ DX12†
DX14
†
Right input 
connector 
 
 
 
 
Rotary switch
 
 
Right output 
connector 
Analog signal input/ 
output connector 
 
 
Rotary switch