Omega Vehicle Security DPiTH-i8DH Fascicule

Page de 2
1
Output 1/Setpoint 1/ Alarm 1 indicator
2
Output 2/Setpoint 2/ Alarm 2 indicator
°C
°C unit indicator for Temperature or Dewpoint
°F
°F unit indicator for Temperature or Dewpoint
%RH Display shows the Percent Relative Humidity
D
Display shows the Dewpoint
a
Changes display to Configuration Mode and advances 
through menu items*
b
Used in Program Mode:
c
Used in Program Mode:
d
Accesses submenus in Configuration Mode and stores 
selected values*
HUMd
YES/NO
tEMP
YES/NO
dEU
YES/NO
UNIt
YES/NO
8
8
CONFIGURATION
FLOW CHART
DESCRIPTION OF FRONT PANEL
The upper display may be RH, Temperature or Dewpoint
readings depending on your Reading Configuration selections.
Factory defaults are shown. The Dual Display allows the user
to observe the Relative Humidity or Dewpoint (upper display)
and Temperature Value (lower display), at the same time.
Disassembly Instruction:
If necessary, the unit may be removed from the panel and
opened.
Warning: Disconnect all ac power from the unit
before proceeding.
1. Remove all wiring connections from the rear of the
instrument, by unplugging the power and input connectors.
2. The meter is front removable from the case 
3. Pull the board assembly out of the case.
WIRING
Wire the instrument according to the figure shown below.
Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow
all instructions and warnings may result in injury!
Refer to Operator’s Manual for important Input Probe
Shield wiring notes
Connect the main power connections as shown in the figure below.
FUSE
Connector Output Type For 115Vac  For 230Vac
DC
FUSE 1
Output 1
Relay
3 A(T)
3 A(T)
FUSE 2
Output 2 
Relay 
3 A(T) 
3 A(T) 
-
FUSE 3
Power 
N/A
100 mA(T) 
100 mA(T)  100 mA(T)
FUSE 4
Power
N/AN/AN/A
400 mA
(T)
This Quick Start Reference provides information 
on setting up your instrument for basic operation. 
The latest complete Communication and Operational
Manual as well as free Software and ActiveX Controls
are available at  www.omega.com/specs/iseries or
on the CD-ROM enclosed with your shipment
.
SAFETY CONSIDERATION
This device is marked with the international
Caution symbol.
The instrument is a panel mount device protected in
accordance with EN61010-1:2001. Remember that the unit
has no power-on switch. Building installation should include
a switch or circuit-breaker that must be compliant to IEC
947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on 
the top of the instrument housing.
• Always disconnect power before changing signal and 
power connections.
• Do not use this instrument on a work bench without 
its case for safety reasons.
• Do not operate this instrument in flammable or 
explosive atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables. 
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the 
instrument if EMC problems persist. 
MOUNTING
Panel Mounting Instruction:
1. 
Using the dimensions from the panel cutout shown in 
exploded views, cut an opening in the panel. 
45mm 
+.61/-.00
x 92mm 
+.81/-.00
with R 1.5, 4 places 
(1.772”
+.024/-.000
x 3.622”
+.032/-.000
with R 0.06”, 4 places)
Panel thickness: 6.4mm (0.25”) max / 0.8mm (0.03”) min.
2. Remove sleeve from the rear of the case by removing
thumbnuts.
3. Insert the unit into the opening from the front of the panel, so
the gasket seals between the bezel and the front of the panel.
4. Slip the sleeve over the rear of the case.
5. Tighten the thumbnuts to hold the unit firmly in the panel.
_____
Underline denotes factory default setup
START HERE
Rear View
DPiTH-i8DH shown
with -2 Probe
DPiTH-i8DV shown
with -5 Probe
Front Views
Button Function in Configuration Mode
• To enter the Menu, the user must first press 
a
button.
• Use this button to advance/navigate to the next
menu item. The user can navigate through all the
top level menus by pressing 
a.
• While a parameter is being modified, press 
a to
escape without saving the parameter.
• Press the up 
b button to scroll through “flashing”
selections. When a numerical value is displayed
press this key to increase value of a parameter
that is currently being modified.
• Pressing the 
b button for approximately 3 seconds
will speed up the rate at which the set point value
increments.
• In the Run Mode, pressing the 
b button changes
display from RH readings to Temperature
readings.
• Press the down 
c button to go back to a previous
Top Level Menu item. 
• Press this button twice to reset the controller to the
Run Mode. 
• When a numerical value is flashing (except set point
value) press 
c to scroll digits from left to right
allowing the user to select the desired digit to modify.
• When a setpoint value is displayed press 
c to
decrease value of a setpoint that is currently being
modified. Pressing the 
c button for approximately
3 seconds will speed up the rate at which the
setpoint value is decremented.
• In the Run Mode, pressing the 
c button changes
from RH readings to Dewpoint readings.
• Press the enter 
d button to access the submenus
from a Top Level Menu item.
• Press 
d to store a submenu selection or after
entering a value - the display will flash a 
STRD
message to confirm your selection.
• In the Run Mode, press 
d twice to enable Standby
Mode with flashing 
STBY.
CONFIGURATION
The instrument has two different modes of operation. Run
Mode: used to display Temperature and Relative Humidity.
Menu Configuration Mode: used to navigate through the menu
options and configure the controller.
a
MENU
b
(UP)
c
(DOWN)
d
ENTER
Output 1 and 2 are for -AL Limit Alarm Option only.
DPiTH-i8DH
DPiTH-i8DV