Appendix A.5. 
Panel / Driver Synchronization 
There is no automatic system of synchronizing the Fire Alarm Panels and the data in the 
FieldServer. This is because the FieldServer cannot poll for status information from the panel 
but has to rely on the panel sending messages with changes in status. 
To synchronize the panel to the FieldServer you should push the reset button on the Fire 
Alarm Panel.  When this is done the driver clears all the Data Arrays associated with the 
connections. In this case ‘associated’ means those DA’s used by the Map Descriptors 
logically connected to the serial port on which the message was received. This is the default 
behavior of the driver – however it is possible to limit the Data Arrays which get cleared so 
that only those DA’s associated with the panel which sent the message get cleared. Further 
information is provided in Appendix A.2 
Appendix A.6. 
Connection Status 
This is a passive client driver connected to a Fire Alarm Panel. Normally there are no alarms 
and thus there would be no way for the FieldServer to know if it was still connected to the 
FACP network.  The National Time & Signal panel, however, sends a message at a regular 
interval of approximately one minute. This driver uses this message to monitor and report the 
status of the connection.  
A connection timeout may be specified. Read about the NATSfacp_Timeout  and 
NATSfacp_Status_DA
 connection parameters in section 1.04. 
If the driver doesn’t receive a ‘valid’ message within this timeout period then the driver 
considers the connection as lost. It reports this providing a connection status bit which can be 
monitored by the upstream node. The bit is set to 1 when the connection is good and set to 
zero when the connection is lost. 
 
A ‘valid’ message is one that does not fail parsing. 
 
Appendix A.7. 
Node Status 
If the FACP sends a message that one of its networked panels has a communications failure 
by sending a message with the Trouble String = “CommFail” then the driver reports that 
panel/Node as offline. If the event is restored to normal then the driver reports the node as 
being online. Furthermore, if a valid message is received from a panel in an offline state then 
the driver sets the node status to online.