1. 
Modbus RTU/ Modbus ASCII Description 
The Modbus RTU and Modbus ASCII drivers allow the FieldServer to transfer data to and from 
devices  over  either  RS-232  or  RS-485  using  Modbus  RTU  or  Modbus  ASCII  protocol 
respectively.    The  driver  was  developed  for  Modbus  Application  Protocol  Specification  V1.1a" 
from  Modbus-IDA.   The  specification  can  be found  at 
www.modbus.org
.   The  FieldServer  can 
emulate either a Server or Client.   
 
The information that follows describes how to expand upon the factory defaults provided in the 
configuration files included with the FieldServer. 
 
There are various register mapping models being followed by various vendors 
To cover all these models FieldServer uses the following three Models 
 
•  Modicon_5digit  –  Use this format  where  addresses  are  defined  in  0xxxx,  1xxxx,  3xxxx  or 
4xxxx  format.  A  maximum  of  9999  registers  can  be  mapped  of  each  type.    This  is 
FieldServer driver’s default format. 
•  ADU  –Application  Data  Unit  address.  Use  this  format  where  addresses  of  each  type  are 
defined in the range 1-65536 
•  PDU  –Protocol  Data  unit  address.  Use  this  format  where  addresses  of  each  type  are 
defined in the range 0-65535.  
 
The key difference between ADU and PDU is for example if Address_Type is ADU and address 
is 1, the driver will poll for register 0.  If Address_Type is PDU, the driver will poll for address 1. 
 
Note  1:  If  vendor  document  shows  addresses  in  extended  Modicon  (i.e.  6  digit)  format  like 
4xxxxx then consider these addresses as xxxxx (omit the first digit) and use either ADU or PDU 
 
Note 2: The purpose of providing 3 different ways of addressing the Modbus registers is to allow 
the user to choose the addressing system most compatible with the address list being used.  At 
the protocol level, the same protocol specification is used for all three with the exception of the 
limited address range for Modicon_5digit.