FieldServer FS-8700-66 Manuel D’Utilisation

Page de 29
Page 11 of 29FS-8700-66_GE-SNP Manual 
 
 
 
 
Page 11 of 29 
 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA  Web:www.fieldServer.com 
Tel: (408) 262-2299   Fax: (408) 262-2296   Toll_Free: 888-509-1970   email: support@fieldServer.com 
4.4.2. 
Driver Related Map Descriptor Parameters 
Column 
Title 
Function 
Legal Values 
Node_Name  Name of Node to fetch data from 
One 
of 
the 
Node 
names 
specified 
in 
“Client 
Node 
Descriptor” above 
Data_Type 
Data type 
Discrete Inputs (%I) 
Discrete Outputs (%Q) 
Discrete  Temporaries 
(%T) 
Discrete 
Internals 
(%M) 
Genius  Global  Data 
(%G) 
Analog Inputs (%AI) 
Analog 
Outputs 
(%AQ) 
Registers (%R) 
%SA Discrete 
%SB Discrete 
%SC Discrete 
%S Discrete (%S) 
Length 
Length  of  Map  Descriptor.    Ensure  that  the 
length does not exceed the table in the PLC 
1-1000 
Address 
Starting address of read block / write block.  The 
1
st
  element  of  each  Data  type  Table  is  referred 
to as address one. 
1 , 2 , 3  
Positive 
whole 
numbers 
Format* 
Use  to  override  the  default  format  for  obtaining 
data.  Bit  tables  are  by  default  read  by  reading 
whole  bytes  at  a  time  (If  the  Length  is  10  then 
10 bytes of data are read and placed in 10 Data 
Array locations) 
 
If  you  wish  to  read  bits  instead  then  use  this 
parameter. (If the Length is 10 then 10 bits are 
read and each bit is stored in its own location.) 
Bit, Byte 
 
The  format  for  %AI, 
%AQ  and  %R  cannot 
be changed. 
GE_Func* 
This  parameter  is  only  specified  when  you 
create  a  write  Map  Descriptor  to  change  the 
privilege level. 
 
If  it  is  not  specified  the  driver  assumes  the 
default (RW – Read/Write). 
CPL, RW 
4.4.3. 
Timing Parameters 
Column Title 
Function 
Legal Values 
Scan_Interval 
Rate at which data is polled 
≥0.1s