5. 
Configuring the FieldServer as a GE_SNP Server 
For  a  detailed  discussion  on  FieldServer  configuration,  please  refer  to  the  FieldServer 
Configuration  Manual.  The  information  that  follows  describes  how  to  expand  upon  the  factory 
defaults  provided  in  the  configuration  files  included  with  the  FieldServer    (See  “.csv”  files 
provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer 
to communicate with a GE_SNP Client. 
 
The configuration file tells the FieldServer about its interfaces, and the routing of data required. 
In  order  to  enable  the  FieldServer  for  GE_SNP  communications,  the  driver  independent 
FieldServer  buffers  need  to  be  declared  in  the  “Data  Arrays”  section,  the  FieldServer  virtual 
Node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to 
the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to 
do this can be found below. 
Note  that  in  the  tables,  *  indicates  an  optional  parameter,  with  the  bold  legal  value  being  the 
default. 
5.1. 
Server Side Connection Descriptors 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify  which  port  the  device  is 
connected to the FieldServer 
P1-P8, R1-R2
3
 
Protocol 
Specify protocol used 
SNP 
Baud* 
Specify baud rate 
110  –  115200,  standard 
baud rates only 
Parity* 
Specify parity 
Even,  Odd,  None,  Mark, 
Space 
Data_Bits* 
Specify data bits 
7, 8 
Stop_Bits* 
Specify stop bits 
Handshaking* 
Specify hardware handshaking 
RTS, RTS/CTS, None 
Poll Delay 
Time between internal polls.  
0-3200s, 1s 
 
Example 
 
//    
Server Side Connections 
 
Connections 
Port, 
Protocol, 
Baud, 
Parity, 
Handshaking 
P1, 
SNP, 
19200, 
Odd, 
None 
 
                                                 
3
  Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 