Appendix A. Troubleshooting Tips 
•  Every 2
nd
 message Times Out  A  possible  cause  is  that  the  poll  frequency  is  so  low  that 
the  time  between  polls  is  greater  than  the  Max  Link  Idle  Time  (of  the  PLC).  If  the  time  is 
exceeded  the  connection  is  closed.  Thus  when  the  next  poll  is  received  by  the  PLC  it 
ignores it and hence it times out in the FieldServer. After timing out, the driver re-establishes 
the connection for the next poll.  
•  Very slow Comms Rate  A timer known as the T1 timer is the minimum time that must pass 
before  a  response  to  a  message  can  be  sent.  Both  ends  of  a  SNP  connection  have  their 
own  T1  timer  (hard  coded  in  the  driver).  When  a  connection  is  made  the  timers  are 
exchanged  and  the  larger  of  the  two  is  used.    The  drivers  T1  timer  is  set  to  a  very  small 
number. SNP message #6 indicates the size of the T1 timer. You may need to configure the 
PLC to improve communications. 
•  Multidrop RS-485 networks. 
SNP  protocol  specifies  that  their  may  only  be  one  master 
on  a  network  at  a  time.  When  using  nameless  Nodes  (Node_id=0)  there  may  be  one  and 
only one PLC on the connection.