Appendix C. Advanced Topics 
Appendix C.1.  SNP Node Names 
The following notes describe how the Node name is used when the FieldServer is acting as 
a Server. 
 
When a Client attempts to establish a connection it may do so by sending the name of the 
Node it wishes to connect to or by sending a Null Node name.  
 
If  the  Client  sends  a  Null  Node  name  then  the  FieldServer  will  connect  if  any  SNP  Nodes 
have been defined for the same port as the Client using the Null name.  In such a case the 
Node  must  be  connected  to  a  port  (This  is  not  always  common  with  FieldServer  Server 
configurations). 
 
Example: Client uses Null name connection. In this case Node must be connected to the 
Client’s port; the Node name is ignored and only one SNP Node per port. 
 
Ports 
 
Port, 
baud 
P1  , 
…. 
 
 
Nodes 
 
Node_Name, 
Port 
Node1, 
P1 
 
If  the  Client  uses  the  Node  name  during  a  connection  attempt  then  the  FieldServer  uses 
the name to find a matching Node.  The name must be an exact match.  If a match is found 
then the connection can be established.  In this case the Node does not have to be tied to 
a particular port and thus one Node could respond to different Clients polling it on different 
ports.  If this method is used and the Node is tied to a port then the Client must poll on the 
same port. 
 
Example:  Client  uses  a  specific  name  to  connect.  In  this  case  provided  there  is  a  Node 
with a matching name the connection will be made  
 
Ports 
 
Port, 
baud …. 
P1,   
…. 
 
 
Nodes 
 
Node_Name, 
Protocol  
Node1,         