Cooling System
Cooling is provided by the two Advanced Cooling Modules 
(ACMs) located at the rear of the enclosure. Each of the 
ACM units contain two variable speed fans. The enclosure 
requires four fans for normal operation, but will operate 
correctly with one fan failed (redundancy is lost if one fan is 
failed in either ACM), however, it is recommended that the 
failed fan be replaced as soon as possible. The ACM units 
can be hot swapped. The LS Module monitors and controls 
the speed of each fan. The speed is set depending on the 
ambient temperature and failed status. The fans are set to 
full speed if one fan is failed. The following table shows 
how the fan speed relates to temperature change.
Note: All fans in an enclosure are set to the same speed.
Table 1-1  Fan Speed vs. Temperature Change
ACM Speed
Ambient Temp (
o
C)
Speed 1
0 to 26
Speed 2
26 to 28
Speed 3
28 to 30
Full Speed
30 +