External line reference functionality
The use of an ELR is recommended when the phase angle and magnitude of the
utility feed the drive is expected to transfer the motor to cannot be accurately
predicted from the phase angle and magnitude of the ILR. Such situations can arise
when transferring the motor to a generator, to a utility feed separate from the one
supplying the drive or in certain plants where multiple transformers with varying
loads are involved. See the "Innovation Series Line Transfer Application Guide" for
a complete discussion of issues related to line reference selection.
The following table specifies variables related to the external line reference
functionality.
Variable
Description
Ext ref phase AB
External line reference analog input voltage.
Ext ref feedback
External line reference scaled to represent actual line
voltage.
Motor Equivalent Circuit
The Motor Equivalent Circuit function implements the equivalent circuit of the
motor.
Function configuration
The following table lists the configuration parameters for the Motor Equivalent
Circuit
.
Parameter
Description
Stator hot res R1
Stator hot resistance. Ohms
Stator cold res R1
Stator cold resistance. Ohms
Rotor hot res R2
Rotor hot resistance. Ohms
Rotor cold res R2
Rotor cold resistance. Ohms
Magnetizing react Xm
Magnetizing reactance. Ohms
Stator lkg react X1
Stator leakage reactance. Ohms
Rotor lkg react X2
Rotor leakage reactance. Ohms
Starting react Xst
Starting reactance. Ohms
Rated rotor temp
Rated rotor temperature. Degrees C or Degrees F
Motor ambient temp