  Chapter 3  Paramters/Functions
Innovation Series Medium Voltage GP Type - G Drives GEH-6385
Sequencer Permissives
 Sequencer permissives are used to prevent or allow the drive to run if the permissive
condition exists in the drive. Two types of permissives exist: internal permissives
and application permissives.
 Internal permissives are internal drive conditions that must be satisfied before the
drive will run (for example, DC bus charged must be True before the drive can run.)
 Application permissives allow the user to connect application specific permissive
logic that must be satisfied before the drive will run.
 The main permissive string used by the sequencer is Ready to run. This permissive
must be True for the drive to run, and the details of this permissive are displayed in
the Sequencing diagrams in the drive.
 
Function inputs
 Application Permissive Inputs
Parameter
Description
Run permissive sel
When used, this parameter selects a variable that
populates Run permissive.
When unused, Run permissive is always set to True.
Start permissive sel
When used, this parameter selects a variable that
populates Start permissive when the drive is stopped.
When unused, Start permissive is always set to True
Variable
Description
Run permissive
If False, this permissive will prevent the drive from starting
or stop the drive if it is running.  An alarm, Run permissive
lost
, is generated when the permissive is False.
Start permissive
If False, this permissive will prevent the drive from starting,
but will not stop the drive if it is running.  An alarm, Start
permissive bad
, is generated when the permissive is
False.
X stop active
If True, this permissive will prevent the drive from starting
or will perform an X-Stop if the drive is running.  A Trip
fault, Run req & xstop open, is generated when this
permissive is True, the drive is stopped, and a run is
requested.
(For more information on X stop active, please refer to
Stopping Commands and Modes.)