GEH-6385  Reference and Troubleshooting, 2300 V Drives
Chapter 3  Paramters/Functions  
••••
  3-91
Function description
The Local Speed Reference function is part of the Speed Reference Generation
function. It forms a speed reference signal from the local source (the DDI).
The Local Speed Reference function produces a local speed reference. This becomes
the speed reference used by the Speed Reference Generation function if the drive is
in local mode (when Local mode active is True). Local mode is enabled using the
DDI Remote/Local button.
The local speed reference is formed by adjusting the reference around an initial
value. The initial value is specified by Local speed. To make the adjustment, press
the DDI speed increment (Speed +) and decrement (Speed –) buttons. Using the
increment and decrement buttons sets Local inc command and Local dec command
respectively. The speed reference increases when Local inc command is True and
decreases when Local dec command is True. The rate of change is defined by Local
Inc/Dec rate
. The local speed reference is limited to values between zero and
Applied top RPM.
The calculation of the local speed reference described in the preceding paragraph
applies when Jog request is False. When Jog request is True, the local speed
reference is set to the value of Local jog speed. More information on Jog request is
available in the Sequencer Commands function help.
Related diagrams
  Speed Reference Generation (Ovr_RfSel)
Minimum Speed Limit
The Minimum Speed Limit function prohibits the speed reference from falling below
a specified magnitude.
Function inputs
The following table specifies the input variables of the Minimum Speed Limit
function.
Variable
Description
Minimum speed
input
Speed reference which is the possibly reversed local or
remote speed reference (variable Speed reference). RPM
Function outputs
The following table specifies the output variables of the Minimum Speed Limit
function.
Variable
Description
Minimum speed
output
Speed reference whose magnitude has been clamped to a
minimum value and which is the input to the Critical Speed
Avoidance function (variable Speed avd func input). RPM
Function configuration
The following table specifies the configuration parameters of the Minimum Speed
Limit
 function.
Parameter
Description
Minimum speed
Minimum speed reference magnitude. RPM