Drive Commissioning: Motor Crossover Voltage
Crossover Voltage specifies the voltage above which field weakening occurs. Field
weakening allows the drive to achieve greater motor speeds without increasing
voltage by decreasing the volts per hertz ratio.
Set Crossover Voltage to the appropriate voltage level. If Crossover Voltage is set to
<No Value>, the drive begins field weakening at the voltage specified by Motor
rated voltage
, which was defined previously.
Related functions
  Primary Motor & Application Data
Drive Commissioning: Motor Protection Class
The motor protection class indicates the motor's capacity to run under overload
conditions. The following values are available for the motor protection class:
  Class10:150%for30sec: IEC motors. Motor can withstand 150% overload for 30
seconds.
  Class20:150%for60sec: US standard motors. Motor can withstand 150%
overload for 60 seconds.
  Class30:150%for90sec: Specially designed motors. Motor can withstand 150%
overload for 90 seconds.
The drive uses the protection class information to determine motor thermal
characteristics which are used in protective functions.
Select the motor protection class that corresponds to the motor connected to the
drive.
Related functions
  Timed Overcurrent Detection
Drive Commissioning: Motor Poles
Parameter Motor poles specifies the number of magnetic poles in the motor. If the
correct value is known, enter it. Otherwise leave blank or set to <No Value>, in
which case the drive will calculate the number from motor nameplate data. It is
recommended that the correct value be obtained and entered if parameter Motor
rated rpm
 is less than 900.
Related functions
  Primary Motor & Application Data
Drive Commissioning: Motor Data Sheet
The motor data sheet provides additional motor parameters beyond what is available
on the motor nameplate. This includes equivalent circuit data, winding resistances
and winding inductances. Flux curve data is also often included. If the motor data
sheet is not available for the applied motor, the control will determine the motor
parameters during the tune-up phase.