Drive Commissioning: Tachometer Support
The Innovation Series drive can operate with or without a tachometer. Three
different tachometer modes are available in the drive:
  Tachless control: The tachless motor control algorithm provides motor speed
and torque control without tachometer feedback.
  Tach control and sfb: The tachometer-based motor control algorithm uses
tachometer feedback to provide motor speed and torque control.
  Tachles ctl/Tach sfb: The motor control uses tachometer feedback to provide
motor speed control, but does not use tachometer feedback to provide torque
control.
Select one of the three tachometer modes.
Related functions
  Motor ctrl alg sel
Drive Commissioning: Tachometer Pulses Per
Revolution
Motor tach PPR specifies the number of pulses per one revolution of the digital A-
Quad-B tachometer. The drive performs an internal conversion between basic counts
and quadrature counts, so the quadrature nature of the tachometer does not need to be
considered when setting Motor tach PPR.
Set Motor tach PPR to the number of tachometer pulses per revolution.
Related functions
  Speed Feedback Calculation
Drive Commissioning: Tachometer Loss Protection
If the drive detects the loss of tachometer feedback, it can take one of two actions:
  Trip: The Tach loss trip fault is reported and the drive stops running.
  Alarm: The Tach loss alarm is reported and the drive continues to run using the
tachless motor control algorithm..
Select the action the drive should take in response to the loss of tachometer feedback.
Related functions
  Tach Loss Detection