  Chapter 3  Paramters/Functions
Innovation Series Medium Voltage GP Type - G Drives GEH-6385
Relay outputs
The following table specifies the parameters that configure the relay output test.
Parameter
Description
Relay 1 test
Relay 1 output.
Relay 2 test
Relay 2 output.
Relay 3 test
Relay 3 output.
SS relay driver test
Relay 4 output.
Related diagrams
  Analog and Digital I/O Testing (HWIO_Tst)
Analog Inputs/Outputs and Mapping
Analog Inputs
Two bipolar (
±
10 volts) analog inputs are available at the terminal board (ATB).
Jumpers on the BAIA board connect a burden resistor that allow these inputs to be
used for 4-20 ma references.
Analog in 1 offset and Analog in 2 offset provide a voltage offset adjustment. Analog
in 1 gain
 and Analog in 2 gain can be used to scale the inputs from volts to
appropriate application units. Analog in 1 filter and Analog in 2 filter provide first-
order signal softening at Analog input 1 and Analog input 2.
Loss of 4-20 ma signal can be configured by selecting a lower threshold Analog in 1
flt lev
 and Analog in 2 flt lev and then selecting the appropriate fault type, Analog in
1 flt mode
 and Analog in 2 flt mode.
Analog Outputs
Two bipolar (
±
10 volts) DAC outputs are available at the terminal board (ATB).
The signal to be output is selected by Analog out 1 select. This signal can be offset
by Analog out 1 offset using the same units as the signal to be output. The signal is
scaled for output by setting Analog out 1 scale to the value that will produce +10
volts. The second DAC is configured in a similar manner.
Meters
Four bipolar (
±
10 volts) meter drivers are available for use with the optional meter
assembly. This assembly is connected to the drive at connector J8 on the backplane.
The signal to be metered is selected by Analog meter 1 sel. This signal can be offset
by Meter 1 offset using the same units as the signal to be metered. The signal is
scaled for output by setting Analog meter 1 scale to the value which shall produce
+10 volts.  Meter 1 mode is used to accommodate both 0 - +10 volt meters and -10 -
+10 volt meters. Analog meter 1 scale is unaffected by Meter 1 mode. The remaining
three meters are configured similarly.
Related diagrams
  Analog Inputs / Outputs & Mapping (HWIO_Ana)