D/A channel Manual-Calibration
Step 1: Click the Manual D/A Calibration tab to show the D/A
channel manual calibration panel. Two D/A channels are
individually calibrated . Before calibrating, output desired
voltage from the D/A channels and measure it through an
external precision multimeter.
individually calibrated . Before calibrating, output desired
voltage from the D/A channels and measure it through an
external precision multimeter.
Step 2: For example, choose channel 0; select the Range and select the
wished output voltage code or value from the radio buttons
(Fig. 6-15 and Fig. 6-16).
(Fig. 6-15 and Fig. 6-16).
Figure 6-15 & Figure 6-16: Selecting D/A Range and
Choosing Output Voltage