Quattro DC Drive Parameters A1 
 
34
 
 
Parameter Description 
Units 
Default Range 
Hidden
Item 
Run 
lock
out
ANA OUT 1 
GAIN  
(Digital to Analog #1 Output Gain) 
 
Adjusts 
the scaling for the Analog Output Channel 
#1.   
NOTE: value of 1.0 = 0 to 10VDC signal. 
voltage
output
channel
analog
GAIN
OUT
ANA
OFFSET
OUT
ANA
creates
software
drive
signal
=
×
 
none 
1.0 
0.0 – 10.0 
Y N 
ANA OUT 2 
GAIN 
(Digital to Analog #2 Output Gain)  Adjusts 
the scaling for the Analog Output Channel 
#2.   
NOTE: value of 1.0 = 0 to 10VDC signal. 
 
 
voltage
output
channel
analog
GAIN
OUT
ANA
OFFSET
OUT
ANA
creates
software
drive
signal
=
×
none 
1.0 
0.0 – 10.0 
Y N 
FLT RESET 
DELAY 
(Fault Reset Delay) 
 
When the drive is set 
for automatic fault reset, this is the time 
before a fault is automatically reset. 
sec 
0 – 120 
Y N 
FLT RESETS / 
HOUR 
(Fault Resets per Hour) 
 
When the drive is 
set for automatic fault reset, this is the 
number of faults allowed to be 
automatically reset per hour. 
faults 
0 – 10 
Y N 
UP TO SPD. 
LEVEL 
(Up to Speed Level) 
 
This parameter sets 
the threshold for the up to speed logic 
output.  This is only used to generate the 
up to speed logic output.  Units in percent 
of contract speed. 
%  
80.00 
0.00 –110.00 
Y N 
RUN DELAY 
TIMER 
(Run Recognition Delay Timer) 
 
Allows the 
user to delay the drive’s recognition of the 
RUN signal therefore allow more time for 
the motor contactor to set.  For more 
information, see RUN DELAY TIMER on 
page 37. 
sec 
0.00 
0.00 – 0.99 
Y Y 
AB ZERO SPD 
LEV 
(Auto Brake Zero Speed Level) Sets the 
speed point that will be considered as zero 
speed for the auto brake function.  The 
units are % of contract speed. 
In order to use the Auto Brake Function, a 
logic output needs to be configured for 
AUTO BRAKE (C3), the parameter SPD 
COMMAND SRC(C1) = MULTI-STEP, the 
parameter SPD REF RELEASE (C1) = 
BRAKE PICKED, and the parameter 
BRAKE PICK CFRM(C1) = EXTERNAL 
TB1. 
0.00 
0.00 – 2.00 
Y Y 
AB OFF DELAY 
(Auto Brake Off Delay) 
 
Determines the 
time after zero speed is reached (level 
determined by the AB ZERO SPD LEV 
(A1) parameter) that the Auto Brake logic 
output goes false.   
sec 
0.00 
0.00 – 9.99 
Y Y 
CONTACTOR 
DO DLY 
(Contactor Drop-Out Delay) 
 
When the 
drive controls the motor contacts via 
CLOSE CONTACT logic output, this 
parameter allows the user to delay the 
drive’s dropout of the motor contactor.  
The delay time starts when the speed 
regulator release signal goes false. 
sec 
0.00 
0.00 – 5.00 
Y Y