New Functions in Version V4.02
7
Supplement to the STEP 7 User Manual V4.0
C79000-Z7076-C552-01
Configuring the DP/PA Link
The DP/PA link is a DP slave which for its part (acting as a kind of “master”)
“opens” a PROFIBUS PA for connecting PROFIBUS PA devices.
The PROFIBUS PA must be running at a transmission rate of 45.45 Kbps when
you connect PA devices.
To configure a DP/PA link, proceed as follows:
1. Install the optional package SIPROM; this will enable you to configure the PA
slaves from the “Hardware Catalog” window at a later stage. (The PA slaves are
located in the “PROFIBUS PA” container.)
2. Configure a DP master system.
3. Drag the DP/PA link (IM 157) from the “Hardware Catalog” window (“DP/PA
Link” container) to the DP master system.
4. Select the DP/PA link; the DP slave structure will be displayed in the lower
section of the station window.
5. Slot 4 represents the “master” for the PA devices; double-click on slot 4 to
set the properties of the PA subnet.
6. Click the “PROFIBUS” button and select the subnet with the transmission rate
of 45.45 Kbps (already preset).
7. Then configure the PA devices.
(Proceed as for DP slaves: Use drag & drop to transfer the PA devices from the
“Hardware Catalog” window in the “PROFIBUS PA” container to the PA subnet.)