Emerson Specific Commands
Supported Commands
ATCA-7350 Control via IPMI Programmer’s Reference (6806800H29E)
23
   
2.3
Emerson Specific Commands
The Emerson IPMC supports several commands which are not defined in the IPMI or PICMG 
3.0 specification but are introduced by Emerson: serial output commands.
2.3.1
Serial Output Commands
Activate firmware
0x2C/0x2D
0x35
-
Query self-test results
0x2C/0x2D
0x36
-
Query rollback status
0x2C/0x2D
0x37
-
Initiate manual rollback
0x2C/0x2D
0x38
-
Table 2-14 Supported PICMG 3.0 Commands (continued)
Command
NetFn 
(Request/Response)
CMD
Comments
The firmware upgrade commands supported by the ATCA-7350 are implemented 
according to the PICMG HPM.1 Revision 1.0 specification.
z
Before sending any of these commands, the shelf management software must 
check whether the receiving IPMI controller supports Emerson specific IPMI 
commands, by using the IPMI command 'Get Device ID'. Sending Emerson specific 
commands to IPMI controllers which do not support these IPMI commands will lead 
to no or undefined results.
z
Implementing any of the Emerson specific IPMI commands means that the software 
is not portable to other IPMI controllers that do not use the   IPMC firmware.
Table 2-15 Serial Output Commands
Command Name
NetFn (Request/Response)
CMD
Description
Set Serial Output
0x2E/0x2F
0x15
See 
Get Serial Output
0x2E/0x2F
0x16
See