Real-Time Clock:
 Clock Operation
7-2
1
Seconds register
2
Minutes register
3
Century/Hours register
4
Day register
5
Date register
6
Month register
7
Years register
8
Control register
The M41T00 clock continually monitors the supply voltage (Vcc) for an out of tolerance 
condition. If Vcc falls below switch-over voltage (Vso), the M41T00:
• Terminates an access in progress
• Resets the device address counter
• Does not recognize inputs (prevents erroneous data from being written)
At power-up, the M41T00 uses Vcc at Vso and recognizes inputs.
CLOCK OPERATION
Read the seven Clock registers one byte at a time or in a sequential block. Access the Con-
trol register (address location 7) independently. An update to the Clock registers is delayed 
for 250 ms to allow the read to be completed before the update occurs. This delay does not 
alter the actual clock time. The eight byte clock register sets the clock and reads the date 
and time from the clock, as summarized in 
Table 7-1:
RTC Register Map
Address:
Data:
Function/Range:
D7
D6
D5
D4
D3
D2
D1
D0
BCD Format:
00
ST
10 Seconds
Seconds
Seconds
00—59
01
X
10 Minutes
Minutes
Minutes
00—59
02
CEB
CB
10 Hours
Hours
Century/Hours
0-1/00-23
03
X
X
X
X
X
Day
Day
01—07
04
X
X
10 Date
Date
Date
01—31
05
X
X
X
10 M
Month
Month
01—12 
06
10 Years
Years
Years
00—99
07
OUT
FT
S
Calibration
Control