Omron C200HE Manuel D’Utilisation

Page de 564
450
Address(es)
Function
28000 to 28015
Group-2 High-density I/O Unit Error Flags for Units 0 to F
28200 to 28215
Special I/O Unit Error Flags for Units 0 to F
28300 to 28303
Communications Board Port A Error Code
28308 to 28311
Communications Board Port B Error Code
AR Area
Address(es)
Function
0000 to 0009
Special I/O or PC Link Unit Error Flags
0010
SYSMAC LINK/SYSMAC NET Link Level 1 System Error Flags
0011
SYSMAC LINK/SYSMAC NET Link Level 0 System Error Flags
0012
Rack-mounting Host Link Unit Level 1 Error Flag
0013
Rack-mounting Host Link Unit Level 0 Error Flag
0014
Remote I/O Master Unit 1 Error Flag
0015
Remote I/O Master Unit 0 Error Flag
0200 to 0204
Error Flags for Slave Racks 0 to 4
0205 to 0214
Group-2 High-density I/O Unit Error Flags (AR 0205 to AR 0214 correspond to I/O numbers 0 to 9.)
0215
Group-2 High-density I/O Unit Error Flag
0300 to 0315
Optical I/O Units (0 to 7) Error Flags
0400 to 0415
Optical I/O Units (8 to 15) Error Flags
0500 to 0515
Optical I/O Units (16 to 23) Error Flags
0600 to 0615
Optical I/O Units (24 to 31) Error Flags
0713 to 0715
Error History Bits
1114
Communications Controller Error Flag Level 0
1115
EEPROM Error Flag for operating level 0
1514
Communications Controller Error Flag Level 1
1515
EEPROM Error Flag for operating level 1
9-6
Host Link Errors
These are the response codes (end codes) that may be returned in the response
frame. When two or more errors occur, the end code for the first error will be re-
turned.
End
code
Contents
Probable cause
Corrective measures
00
Normal completion
---
---
01
Not executable in RUN mode
The command that was sent cannot
be executed when the PC is in RUN
mode.
Check the relation between the
command and the PC mode.
02
Not executable in MONITOR
mode
The command that was sent cannot
be executed when the PC is in
MONITOR mode.
03
UM write-protected
The PC’s UM is write-protected.
Turn OFF pin 1 of the CPU Unit’s
DIP switch.
04
Address over
The program address setting in an
SV Read or SV Change command
exceeds the 65,535 maximum.
Correct the program address setting
and transfer the command again.
13
FCS error
The FCS is wrong. Either the FCS
calculation is mistaken or there is
adverse influence from noise.
Check the FCS calculation method.
If there was influence from noise,
transfer the command again.
14
Format error
The command format is wrong or a
command that can’t be divided has
been divided.
Check the format and transfer the
command again.
15
Entry number data error
The data is outside of the specified
range or too long.
Correct the data and transfer the
command again.