5-18-14 LINE TO COLUMN – COLM(64)
S: Source word
IR, SR, AR, DM, HR, TC, LR
C: Column bit designator (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Ladder Symbols
Operand Data Areas
D: First word of the destination set
IR, AR, DM, HR, TC, LR
COLM(64)
S
D
C
@COLM(64)
S
D
C
Limitations
D and D+15 must be in the same data area.
C must be between #0000 and #0015.
Description
When the execution condition is OFF, COLM(64) is not executed. When the
execution condition is ON, COLM(64) copies the 16 bits of word S (00 to 15) to
the column of bits, C, of the 16-word set (D to D+15).
0
0 0 0 0 1 1 1 0 0 0 1 0 0 0 0 1
Bit 
15
Bit 
00
D
C
1 1 0 1 0 0 1 0 0 1 1 1 0 0 0 1
D+1
0 0 0 1 1 0 1 1 0 0 1 0 0 1 1 1
D+2
  .
  .
  .
  .
  .
  .
  .
  .
  .
  .
0 1 1 1 0 0 0 1 1 0 0 0 1 0 1 0
D+15
1 0 0 0 0 0 1 1 0 0 0 0 0 1 1 1
D+3
0 1
1
S
1
Bit 
15
Bit 
00
  .
  .
  .
  .
  .
  .
  .
  .
  .
Flags
ER:
The bit designator C is not BCD, or it is specifying a non-existent bit (i.e.,
bit specification must be between 00 and 15).
Indirectly addressed DM word is non-existent. (Content of 
DM word is
not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the content of S is zero; otherwise OFF.
Example
The following example shows how to use COLM(64) to move the contents of
word DM 0100 (00 to 15) to bit column 15 of the set (DM 0200 to DM 0215).
COLM(64)
DM 0100
DM 0200
#0015
00000
Address
Instruction
Operands
00000
LD
00000
00001
COLM(64)
DM
0100
DM
0200
#
0015
Data Conversion