Omron C200HX Manuel D’Utilisation

Page de 564
478
Response Format
@
W
#
x 16
0
x 10
0
x 10
1
x 16
1
Node no.
Header
code
End code
Terminator
FCS
Limitations
The command can’t be executed unless the SV is BCD from 0000 to 9999.
The command can’t be executed if the UM area is write-protected.
If the same instruction is used more than once in a program, the SV of the first
one will be changed.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
---
OK
OK
---
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
An end code of 15 (entry number data error) will be returned if the SV isn’t BCD or
the mnemonic/TC number is incorrect.
An end code of 16 (command not supported) will be returned if the specified
instruction doesn’t exist in the program.
End code
Contents
00
Normal completion
01
Not executable in RUN mode
13
FCS error
14
Format error
15
Entry number data error
16
Command not supported
18
Frame length error
23
User memory protected
10-3-21
SV CHANGE 2 –– W$
Changes the contents of the second word of the TIM, TIMH(15), CNT,
CNTR(12), or TTIM(87) at the specified program address in the user’s program.
This can only be done with a program of less than 10K.
Command Format
OP4
OP3
OP2
OP1
@
W
$
x 10
0
x 10
0
x 10
1
x 10
3
x 10
2
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
OP4
OP3
OP2
OP1
x 10
0
x 10
3
x 10
2
x 10
1
Node no.
Program
address
Mnemonic
Timer/counter
(0000 to 0511)
Header
code
Operand
SV
Terminator
FCS
Host Link Commands
Section 10-3