Omron C200HX Manuel D’Utilisation

Page de 564
496
Limitations
The registered data is checked from the beginning and the data will be regis-
tered up to any errors. For example, if a command attempts to register 129
items, a frame length error (end code 18) will occur but the first 128 items will be
registered.
DM 6656 to DM 6999 do not exist, but an error will not occur if you try to register
these words.
Bits and words can be specified in any order and they will be registered in the
order that they were specified.
The data can be divided into multiple frames.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
OK
OK
OK
OK
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
OK
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect or the “,” data break between two items is omitted.
An end code of 15 (entry number data error) will be returned if the “Read area,”
“Read word address,” or “Data format” setting is incorrect.
End code
Contents
00
Normal completion
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
19
Not executable
A3
Aborted due to FCS error in transmit data
A4
Aborted due to format error in transmit data
A5
Aborted due to entry number data error in transmit data
A8
Aborted due to frame length error in transmit data
10-3-36
COMPOUND COMMAND DATA READ –– QQIR
The bit, word, and timer/counter status is read as a batch according to the read
information that was registered with QQMR.
Command Format
@
Q
Q
x 10
0
x 10
1
I
R
Node no.
Header
code
Sub-header
code
Terminator
FCS
Host Link Commands
Section 10-3