Omron C200HG Manuel D’Utilisation

Page de 564
488
10-3-28
MULTIPLE FORCED SET/RESET –– FK
Force sets, force resets, or cancels the forced status of the bits in one word in the
IR, SR, LR, HR, or AR, or a timer/counter Completion Flag.
Command Format
@
F
K
x 10
0
x 10
1
x 10
3
x 10
2
x 10
1
x 10
0
OP1 OP2 OP3
OP4
15
14
13
12
11
10
1
0
Node no.
Header
code
Operand
Word 
address
Forced set/reset/cancel data
Bit
Terminator
FCS
For data areas IR, SR, LR, HR, and AR, the “Operand” parameter indicates the
data area where the bit will be force-set and the “Word address” parameter indi-
cates the word address.
For the TC area, “Operand” parameter indicates the mnemonic of the timer or
counter instruction and the “Word address” parameter indicates the TC number.
Data area/
Operand
Word
Bit
instruction
OP1
OP2
OP3
OP4
address
IR or SR
C
I
O
(Space) 0000 to 0511
00 to 15
LR
L
R
(Space) (Space) 0000 to 0063
HR
H
R
(Space) (Space) 0000 to 0099
AR
A
R
(Space) (Space) 0000 to 0027
TIMER
T
I
M
(Space) 0000 to 0511
Always
HIGH-SPEED TIMER
T
I
M
H
00
COUNTER
C
N
T
(Space)
REVERS. COUNTER
C
N
T
R
TOTALIZING TIMER
T
T
I
M
TRANSITION FLAGS
T
N
(Space) (Space) 0000 to 1023
The 16 bytes of forced set/reset/cancel data specifies what operation will be per-
formed on the specified data area word or Completion Flag. If a timer or counter
is specified, the status of the Completion Flag is force-set or force-reset using
the setting for bit 15, and the settings for bits 00 through 14 will be ignored. Only
force-setting and force-resetting are possible for timers/counters.
Forced set/reset/cancel data
Operation
0000
Bit status not changed
0010
Reset to 0.
0011
Set to 1.
0100
Forced-reset
0101
Forced-set
1000
Cancel forced set/reset status
Response Format
@
F
K
x 10
0
x 10
1
x 16
1
x 16
0
Node no.
Header
code
Terminator
FCS
End code
Host Link Commands
Section 10-3