Siemens LU01 Manuel D’Utilisation

Page de 114
Page 96
SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
mmmm
m
Te
c
h
n
ical Ref
e
re
nce
Status B
1 character, $0 to $F (convert to binary, e.g. scan point is in high alarm) 
Status C
1 character, $0 to $F (convert to binary, e.g. scan point is not in rate or band alarm) 
MT-01 Hold Message 
Field Name
Definition
Temp
2 characters, $32 to $FA (convert to decimal and subtract 100, e.g. tempera-
ture = 20 °C) 
Percent
5 characters, 00.00 to 9999. (e.g. current level = 85.00% of span, EEEE. = field 
overflow) 
End Of Message
CR ($0D) 
Field Name
Definition 
Start Of Message STX ($02) 
Message Type
2 characters, 01 (indicates the SITRANS LU01 was removed from the 
RUN mode) 
End Of Message
CR ($0D) 
# # # #
1 = low low alarm
1 = low alarm
1 = high alarm
1 = high high alarm
MSB
LSB
# # # #
1 = rate alarm 2
1 = rate alarm 1
1 = band alarm 1
1 = band alarm 2
MSB
LSB
start of message
message type
end of message