If the preceding remedies have not produced satisfactory results, the false echo has to be 
ignored. Extend Near Blanking (P800) to a distance (from the transducer face) to just 
beyond the distance represented by the Reading. This also increases the nearest 
distance the material level/object may come within the transducer face and still be 
detected. 
If increasing Near Blanking is unacceptable (the transducer cannot be mounted higher) 
see Auxiliary Transducer (P725). Otherwise, the TVT Curve must be raised in the area of 
the false echo. 
Connect an oscilloscope to the SITRANS LU01, ( see Enhancement Parameters Scope 
Displays, P810). Adjust the TVT Start Min (P833), TVT Start Duration (P834), and TVT Slope 
Min (P835) slightly. 
Continue making minor TVT Curve adjustments and taking new measurements while 
observing the Echo Marker position until the Echo Lock Window repeatedly locks onto 
the true echo. Verify the false echo is still ignored, regardless of the vessel material level, 
or empty/fill activity. 
Wrong Reading 
If the Reading is erratic, or jumps to some incorrect value periodically, ensure the: 
1.
Material (object) surface monitored, is not beyond the transducers maximum range. 
2.
Material is not falling in the transducer sound beam. 
3.
Material (P002) value matches the material monitored. 
4.
Measurement Response (P003) is not set too fast. 
5.
Transducer (P004) type entered matches the transducer used. 
If the periodic incorrect value is always the same, see Fixed Reading. If the incorrect 
value seems to be random, verify the material surface to transducer distance is less than 
the Empty value entered plus 20%. If the material/object monitored is outside this 
distance, increase Range Extension (P801) as required. 
If the material monitored is a liquid, check for splashing in the vessel. Decrease 
Measurement Response (P003) as required to stabilize the Reading, or install a stilling 
well (contact Milltronics or your local distributor). 
Access the Noise (P807) parameter. If the peak value jumps wildly, verify the transducer 
cable shields are connected to the SITRANS LU01 shield terminals and not to ground 
elsewhere. 
If the SITRANS LU01 is mounted in close proximity to (or transducer cables run near 
those of) another ultrasonic level monitor, see Level System Sync (P726). 
Temporarily disable nearby SCR control drives, high voltage or current contactors. If the 
condition disappears, move the SITRANS LU01 to another location. 
Set Echo Lock (P711) to "max verification" (response to material level changes may be 
slowed somewhat).