Siemens LU01 Manuel D’Utilisation

Page de 114
Page 16
SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
mmmm
m
Inst
allat
ion
Communication
Serial
SmartLinx
Refer to the appropriate SmartLinx manual for installation and wiring.
Level System Synchronization 
Avoid mounting the SITRANS LU01 near another ultrasonic level monitor. Likewise, when 
more than one monitor is installed within a single plant/facility, ensure the transducer 
cables of each system are run in separate grounded metal conduits. If this system 
separation is impractical, or if measurement difficulties are encountered, system 
synchronization may be required. 
Synchronize the SITRANS LU01 with another SITRANS LU01 
1.
Mount the level monitors together in one cabinet. 
2.
Ensure the level monitors share a common power (mains) supply, and ground 
(earth). 
3.
Interconnect the SYNC terminals of the level monitors to be synchronized. 
Notes:
The communication protocol is automatically detected by the SITRANS LU01 
and shown via LED on the motherboard.
Ground shield at one end only.
Note: 
To synchronize the SITRANS LU01 with other Siemens Milltronics 
ultrasonic level monitors, contact Siemens Milltronics or your local distributor. 
RS-232
RS-485
to customer device,
RS-232 port
15 m (50ft) max
to customer device,
RS-485 port
1200 m (4,000 ft) max