SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
Custom Relays (P111 to P113) 
P111 Relay Control Function
Sets the control algorithm used to trip the relay.
When accessed, the Parameter Type display changes to the Relay symbol and the Index 
display changes to the Relay Number (corresponding to the SITRANS LU01 terminals).
Use zero 0 (preset) to disable control of the indexed relay.
To enter a relay designation: 
1.
Press 
 to display the Auxiliary Function symbol, 
2.
Press 
 or 
 to scroll access the desired relay designation and... 
3.
Press . 
 
Refer to Point Alarm and Status section in SmartLinx instruction manuals for more 
information.
Primary Index
Relay
Values
See chart on next page
Altered by
P100 Preset Applications
Note: 
All relay ON/OFF points must be referenced from Empty (P006), regardless 
of Operation Mode selection (POO1).
Function
Designation
Operation
Level
LL, L, H, or HH
Similar to Standard Alarms but with Relay ON/OFF Setpoints
In Bounds
b1 or b2
1
1.
The relay designation is not displayed but is included in the data message.
Alarms when level is between the Relay ON/OFF Setpoints
Out of Bounds b1 or b2
1
Alarms when level is not between the Relay ON/OFF Set-
points
Rate
r1 or r2
1
Level rate of change alarm with Relay ON/OFF Setpoints
Temperature
Not applicable
Alarm is activated by independent Relay ON/OFF Setpoints
LOE
Not applicable
Relay de-energizes in the event of Failsafe timer (P700) expiry
Cable fault
Not applicable
Relay de-energizes under transducer short or opened condi-
tion
Pump
Not applicable
With independent Relay ON/OFF Setpoints
Note: 
When the Relay Function is altered, affected Alarm Parameters (P101 to 
P104) display "ch" (changed) when accessed. Use the Relay ON/OFF Setpoints 
(P112/P113) instead.