SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
For IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a 
dead band prevents relay chatter due to material level fluctuations at both the upper and 
lower setpoints.
Independent Relay Failsafe (P129) 
P129 Relay Failsafe 
Sets the failsafe operation per relay to allow for more flexible programming.
Use this for operations independent of the Failsafe Material Level (P070). 
Relay Failsafe is only available for the following relay functions (P111) and is not used for 
any other relay control function. 
To select an independent Relay Failsafe value:
1.
Press FUNCTION 
 to display the Auxiliary Function symbol. 
2.
Press ARROWS 
 
 to scroll through the failsafe options.
3.
Select option and press ENTER 
.
Enter the dead band in either percent of 
span or units of measure (P005). The 
deadband value is applied both above 
and below the upper and lower bound 
setpoints as shown in the figure.
Primary Index
Relay
Values
OFF
*
Response governed by P071 Failsafe Material Level
HOLd
For LAST KNOWN relay state retention
dE
To have the relay de-energize immediately on failsafe
En
To have the relay energize immediately on failsafe 
Altered by
P071 Failsafe Material Level
Related
P070 Failsafe Timer
P111 Relay Control Function
Relay Function (P111)
Preset (P129)
1 – level alarm
OFF
2 – in bounds alarm
3 – out of bounds alarm
4 – rate of change alarm
5 – temperature alarm
50 – all pump controls
dE
Actual ON or OFF setpoint
Actual OFF or ON setpoint
P116, deadband
P116, deadband
Setpoint set in P112 or P113