Peripheral Communication Support Parameters 
(P740 to P749)
P740 Peripheral Communications 
Use this feature to select the SITRANS LU01 to communication message format. 
P748
 RS-485 Termination
Single point termination may be required to minimize transmission reflections, on long 
cable runs typical of 500 m or more.
P749
 Serial Bus Type
Displays the type of communication bus the SITRANS LU01 is currently set for. If there is 
no connection, the SITRANS LU01 defaults to RS-485. If a bus type other than RS-485 is 
connected, the SITRANS LU01 displays the type of bus it is, or is attempting to, 
communicate with.
SmartLinx Reserved (750 to 769) 
These parameters are reserved for optional SmartLinx communications cards and vary by 
card. Refer to the SmartLinx documentation to determine if any of them are used.
Values
0
Off
if comm port is not used, OFF increases LU01 pro-
cessing speed.
1
*
normal 
messages 
(preset)
messages transmitted as a continuous string of 
characters
2
formatted 
messages 
commas inserted between message fields for 
easier message distinction
Note: 
Refer to Technical Reference / Communication Support on page 94 if 
Peripheral Communication is required.
Values
0
* Off
1
 
on
Values (view only)
232
RS-232
485
* RS-485: default when nothing is connected
bPL
bipolar current loop
rJ11
for Siemens Milltronics use