Use this feature, when monitoring solids (P002 = 2), if the reported level fluctuates 
slightly, though the monitored surface is still. Enter the amount (in ms) of long shot Echo 
Profile smoothing required. When a value is keyed in, the nearest acceptable value is 
entered.
P825 Echo Marker Trigger
The point on the primary echo on which the measured value is based.
Use this feature if the reported material level fluctuates slightly, due to a variable rise in 
the leading edge of the true echo on the Echo Profile.
Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the 
Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo. 
This value is preset to 90% when P002=1 (Liquid) or 50% when P002=2 (Solid).
Advanced TVT Adjustment (P830 to P835) 
Advanced TVT control applies to long shots only.
P830 TVT Type
Selects the TVT Curve used.
Values
Range: 5 to 95%
Preset: 90% when P002=1 (Liquid) or 50% when P002=2 (Solid)
Related
P817 Profile Pointer Time
P818 Profile Pointer Distance
P819 Profile Pointer Amplitude
P820 Algorithm
P821 Spike Filter
P822 Narrow Echo Filter
P823 Reform Echo
Note: 
The following parameters are for authorized Siemens Milltronics Service 
personnel or technicians familiar with Siemens Milltronics echo processing 
techniques.
Values
1
TVT  Short  Curved
2
TVT Short Flat
3
TVT  Long  Flat
4
TVT Long Smooth Front
5
TVT Long Smooth
6
TVT  Slopes
Altered By
P002  Material
Related
P805 Echo Confidence
P835 TVT Slope Min