Schneider Electric vw3-a58101 Manuel D’Utilisation

Page de 294
75
ENGLISH
Adjust Menu
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller 
identification label for high torque applications.
Code
Description
Adjustment range
Factory setting
S
S
S
Sd
d
d
dC
C
C
C
DC stop.curr - A
0.1 to 1.36 In (1)
Acc. to contr. rating
Injection braking current applied after 30 seconds if tdC = Cont.
Check that motor will withstand this curr. without overheating
J
J
J
JP
P
P
PF
F
F
F
Jump Freq.  - Hz
0 to HSP
0 Hz
Skip frequency : prohibits prolonged operation over a frequency range of +/-2.5 Hz around JPF. This 
function can be used to prevent a critical speed which causes resonance.
J
J
J
JF
F
F
F2
2
2
2
Jump Freq.2 - Hz
0 to HSP
0 Hz
Second skip frequency: Same function as JPF, for a second frequency value
J
J
J
JF
F
F
F3
3
3
3
Jump Freq.3 - Hz
0 to HSP
0 Hz
Third skip frequency: Same function as JPF, for a third frequency value
U
U
U
US
S
S
SC
C
C
C
Machine Coef.
0.01 to 100 
1
Coefficient applied to parameter rFr (output frequency applied to the motor), the machine speed is 
displayed via parameter USP
USP = rFr x USC
t
t
t
tL
L
L
LS
S
S
S
LSP Time     - s
0 to 999.9 
0 (no time limit)
Operating time at low speed. After operating at LSP for a given time, the motor is stopped 
automatically. The motor restarts if the frequency reference is greater than LSP and if a run 
command is still present.
Caution : value 0 corresponds to an unlimited time
GP_ATV58_EN.fm  Page 75  Mardi, 2. avril 2002  6:09 18