MN/CDM570L.IOM 
2.2 Mounting 
If the CDM-570/570L is to be mounted in a rack, ensure that there is adequate clearance 
for ventilation, particularly at the sides. In rack systems where there is high heat 
dissipation, forced air cooling must be provided by top or bottom mounted fans or 
blowers. Under no circumstance should the highest internal rack temperature be allowed 
to exceed 50°C (122°F). 
 
IMPORTANT
 
The CDM-570/570L CANNOT have rack slides mounted to the side of 
the chassis. 
Two cooling fans are mounted on the right-hand side of the 
unit. However, Comtech EF Data recommends that an alternate method of 
support within the rack be employed, such as rack shelves. If there is any 
doubt, please consult the Comtech EF Data Customer Support department. 
 
2.2.1 Optional 
Rear-Mounting Installation Bracket 
 
Table 2-1.  Optional Mounting Kit , KT/6228-2 
Quantity  Part Number 
Description 
FP/6138-1 
Bracket, Rear Support  
HW/10-32x1/2RK 
Bolt, #10 Rack 
HW/10-32HEXNUT
Nut, #10 Hex 
4 HW/10-32FLT  Washer, 
#10 
Flat 
2 HW/10-32SPLIT Washer, 
#10 
Split 
HW/10-32SHLDR 
Screw, Shoulder #10 
 
 
The tools required for this installation are a medium Phillips
 screwdriver, and a  
5/32-inch SAE Allen
 Wrench. 
 
Refer to the following Figure, then install the Modem rear support brackets as follows: 
 
a)  Install the rear support brackets onto the mounting rail of the rack. Fasten with the 
bracket bolts. 
 
b)  Mount the modem into the equipment rack ensuring that the socket heads engage into 
the modem slots of the rear support brackets. 
 
c)  Fasten the provided #10 shoulder head screws to the rear-side mounting slots on 
either side of the chassis modem and secure with #10 flat washers, #10 split washers, 
and #10 hex nuts. 
 
  
 
2–2