Hardware
7-15
CSN14/HV/S  
High Voltage Card with Safety Jack Connectors
The CSN14/HV/S card contains 16 differential input channels and is for use with “safety jack” type connectors. Each
CSN14/HV/S card is capable of measuring analog input signals on any of the following three programmable ranges:
±2.5 volt, ±25 volt and ±250 volt.
CSN14/HV/S,  High Voltage Card with Safety Jack Connectors
Number of Inputs:
16 differential; programmable by channel for input range
Input Connectors:
Safety Jack
Voltage Range, Accuracy and Resolution:
 
±
 2.5V;
±
 0.02%;
78.14 
µ
V/bit
 
±
 25 V;
±
 0.02%;
781.4 
µ
V/bit
 
±
 250 V;
±
 0.02%;
7.81 mV/bit
Digital Filtering:
      Used for AC line cycle noise rejection.
      Selectable off, 1-256 samples in a binary count.
Temperature Coefficient:  
<
 0.01%/
°
C
Input Impedance:  10 M
Ω
 typical
Input Bias Current:    20 pA maximum.
Maximum Common Mode Voltage:
1
  500 VDC or 500 VAC peak
Maximum Normal Mode Voltage: 500 VDC or 500 VAC peak
Common Mode Rejection:    100 dB typical.
Maximum Allowable Input:  500 VDC or 500 VAC peak
Channel-to-Channel Isolation:
                
500 VDC or 500VAC peak
Channel-to-Power Ground Isolation:
2
               500VDC or 500 VAC peak
Note 1:
Specified for coupling impedance >30 M
Ω
 and common mode frequency < 60 Hz.  700 VDC or 700 VAC peak ; 325 VDC
or 325 VAC peak if used in the same system with a MTC/24 scanning module, before equipment damage occurs.
Note 2:
325 VDC or 325 VAC peak if used in the same system with a MTC/24 scanning module.