Omnitron Systems Technology CWDM/AD Fascicule

Page de 2
Channel Port (Left and Right)
The Channel Ports transmit and receive signals on a specific CWDM wavelength. 
The Channel Ports are multiplexed on and demultiplexed from the Common Ports.  
As shown in Figure 3 and 4, a 1-Channel CWDM/AD supports a single channel in 
both directions and a 2-Channel CWDM/AD supports two channels in both directions.  
Each Channel Port has a Left and Right port.  Data transmitted and received by 
Channel Port Left is aggregated on Common Port Left and data transmitted and 
received by Channel Port Right is aggregated on Common Port Right.  
CWDM / AD
2 - 4
CWDM/X
1
2
3
4
CWDM/X
1
2
3
4
1
(Left)
1
(Right)
COM-L
COM-R
Figure 3: 1-Channel Add/Drop MUX/DEMUX
COM-L
COM-R
CWDM / AD
1
(Left)
1
(Right)
3 - 4
CWDM/X
1
2
3
4
CWDM/X
1
2
3
4
2
(Left)
2
(Right)
Figure 4: 2-Channel Add/Drop MUX/DEMUX
NOTE:  For more information on the 
iConverter
 CWDM/X modules, visit Omnitron’s 
website at: http://www.omnitron-systems.com 
Common Port (Left and Right)
The Common Ports transmit and receive the aggregated wavelengths connected to 
the Channel Ports.  As shown in Figures 3 and 4, there are Left and Right  Common 
Ports on the CWDM/AD module. Common Port Left (COM-L) and Common Port 
Right (COM-R) are internally connected to pass through all wavelengths not dropped 
or added by the specific CWDM/AD model. Only the specific wavelength of the 
model selected will be dropped to the appropriate Channel Port.  Common Port 
Left drops and adds wavelength traffic from Channel Port Left and Common Port 
Right drops and adds wavelength traffic from Channel Port Right. 
Page 2
Installation
1.  Carefully  slide  the  module  into  an  open  slot  in  an 
iConverter
  chassis. Align 
the  module  with  the  installation  guides  and  ensure  that  the  module  is  firmly 
seated against the backplane. Secure the module by fastening the front panel 
thumbscrew (push in and turn clockwise to tighten) to the chassis front. The 
CWDM/AD  module  requires  no  external  power,  however,  if  management  is 
required, the module must be installed in an 
iConverter 
powered chassis with a 
Network Management Module (NMM2 Model 8000N-1).
2.  Connect a single-mode, dual fiber duplex LC cable between the Channel Port of 
the CWDM/AD module and the attached device.  It is important to ensure that the 
wavelength of the CWDM/AD matches the wavelength of the attached device.  
When  connecting  the  Channel  Port,  make  sure  the  Left/Right  designation  is 
followed. This will ensure the data from the Channel Port is aggregated onto the 
corresponding Common Port. Ensure that the transmit (Tx) is attached to the 
receive side of the device at the other end, and the receive (Rx) is attached to 
the transmit side.
3.  Connect  a  single-mode,  dual  fiber  duplex  LC  cable  between  the  Common 
Ports on the CWDM/AD module(s) (this connection may be made through fiber 
patch panels since the modules may not be co-located) or CWDM/X devices.  
When connecting between the Common Ports on the CWDM/AD modules, it 
is recommended to connect the Common Port Right (COM-R) to the Common 
Port Left (COM-L) on the other CWDM/AD module. Ensure that the transmit 
(Tx)  is  attached  to  the  receive  side  of  the  device  at  the  other  end,  and  the 
receive (Rx) is attached to the transmit side.
NOTE:  For proper installation, a network diagram indicating port designations is 
recommended.
NOTE:  The 
iConverter
 CWDM/AD modules can not be installed in slots 4, 8, 12 and 
16 of a 19-Module Chassis or in the top slot of a 2-Module Chassis or in a 1-Module 
Redundant Power Chassis.
Design Considerations
iConverter 
CWDM/AD modules are passive devices that require no external power.   
Attenuation (signal loss) of less than 1.9dB will be realized through each port on the 
module (see the CWDM/AD Data Sheet for exact loss specification for each model).  
Detailed calculations should be performed for each fiber optic link in the network to 
ensure the proper optical devices are specified with sufficient transmitter power.  
When calculating optical loss, ensure that the total loss, plus a safety factor (typically 
3dB), does not exceed the optical power budget.  The optical power budget is the 
difference between the transmitter optical output power and the receiver’s optical 
sensitivity. 
The transmitter optical output power and receiver optical sensitivity values can be 
obtained from the manufacturers of the respective equipment.  Please consult the 
iConverter
 data sheets for CWDM/AD signal loss specifications.
Page 3