Troubleshooting Using Indicators
Section 9-1
• Setting hardware switches.
Indicators
Probable cause
Probable remedy
RUN
ERC
ERH
INS
Lit
Not lit Not lit Lit
Unit operating normally; 
Network participation nor-
mal.
---
Not lit Lit
---
---
Controller Link Unit faulty.
If the ERC indicators still 
lights when the Unit is 
mounted on another PLC, 
replace the Controller Link 
Unit.
Not lit Not lit Not lit Not lit Power is not being sup-
plied correctly to the PLC.
Check the power supply 
voltage and supply at the 
recommended voltage.
The Controller Link Unit 
has become loose.
Secure the Controller Link 
Unit firmly.
The Controller Link Unit is 
mounted in the wrong slot.
Refer to  CVM1 and CV-
series PLCs
 
and mount the 
Unit correctly.
The Controller Link Unit is 
faulty.
If the indicators do not light 
when the Unit is mounted 
in another PLC, replace 
the Controller Link Unit.
Lit
Lit
---
Not lit The node address is out-
side the setting range.
Reset the node address to 
within the 1 to 32 range.
The same node address is 
being used by two different 
Units.
Reset so that each node 
address is used only once 
within the same Network.
Lit
---
Lit
---
Routing table setting error 
or a Routing Table Enable/
Disable Bit setting error.
Remake and set the rout-
ing table correctly, referring 
to 7-4 Setting Routing 
Tables
. When no routing 
table is being used, set the 
Routing Table Enable/Dis-
able Bit to OFF.
The Unit is mounted to a 
non-compatible PLC.
Refer to 1-2-4 Controller 
Link Unit Models and PLCs
 
and reinstall the Unit on 
the appropriate PLC.
An error has occurred in 
the PLC.
Refer to the PLC’s opera-
tion manual and correct 
the error. If the error occurs 
again, replace the PLC.
EEPROM error
Refer to 9-2 Status Area 
and Troubleshooting
, cor-
rect the data where the 
error has occurred, and 
reset the Unit. If the error 
occurs again, replace the 
Controller Link Unit. 
The unit number is not set 
in the range from 0 to 15.
Reset the Unit number to 
within a range of 0 to 15.
The same unit number is 
set more than once for the 
same PLC.
Reset so that each unit 
number is set only once 
within the same PLC 
(including the Expansion 
CPU Backplane.)
I/O tables have not been 
created for the PLC or they 
are faulty.
Create I/O tables for the 
PLC correctly.