185
Ladder Programming with Tag Data Links
Section 6-3
Programming for Revision 1 or Higher
Example of Programming 
to Process Data
The following type of programming can be used to process data only when the
data links are operating normally. 
Interlocks (IL and ILC instructions) and jumps (JMP and JME instructions) can
also be used to process data only when the data links are operating normally
as shown below. 
Tag Data Link 
Operating
n+11 bit 01
Unit Error  
Occurred
n+10 bit 00
Unit Error 
Occurred
n+10 bit 00
10000
Local node 
Error output 
Release Flag 
Local node  
Error output 
DIFD 
10000
DIFU 
10000
The parts of the ladder program 
that use the data link area for 
the relevant node are processed 
only when the corresponding 
Normal Operation Flag is ON.
Normal Operation 
Flag 
Additional part
Normal Operation 
Flag 
Node A data processing
Node A Data Link 
Normal Operation Flag 
IL
ILC
Node B data processing
Node B Data Link 
Normal Operation Flag 
IL
ILC
Node C data processing
Node C Data Link 
Normal Operation Flag 
IL
ILC