CANopen Communication Module DVPCOPM-SL 
DVP-PLC Application Manual 
24 
Required settings in DVPCOPM-SL: 
Parameter 
Setting 
Explanation 
Node address 
01 
Set the node address of DVPCOPM-SL to “01”. 
Baud rate 
1 Mbps 
Set the communication speed between DVPCOPM-SL and 
bus to “1 Mbps”. 
Required settings in IFD9503: 
Parameter 
Setting 
Explanation 
Node address 
02 
Set the node address of IFD9503 to “02”. 
Baud rate 
1 Mbps 
Set the communication speed between IFD9503 and bus to 
“1 Mbps”. 
Required settings in VFD-B AC motor drive: 
Parameter 
Setting 
Explanation 
02-00 
04 
The main frequency is operated by RS-485 interface. 
02-01 
03 
The running command is operated by communication 
interface. Operation by keys is valid. 
09-00 
01 
Communication address of VFD-B: 01 
09-01 
03 
Baud rate: 38,400 bps 
09-04 
03 
Modbus RTU mode, format <8, N, 2> 
Devices in PLC: 
Explanation 
PLC device 
Content 
15 14 13 12 11 10 9
8
7  6  5  4  3
2
1
0
D6250 
0101Hex
ReqID = 01Hex 
Command = 01Hex 
D6251 
0004Hex
Reserved 
Size = 04Hex 
D6252 
0102Hex
Type = 01Hex 
MAC ID = 02Hex 
D6253 
2021Hex
High byte of index = 20Hex
Low byte of index = 21Hex
SDO request 
message 
editing area 
D6254 
0004Hex
Reserved 
Sub index = 04Hex 
D6000 
0101Hex
ReqID = 01Hex 
Status = 01Hex 
D6001 
0006Hex
Reserved 
Size = 06Hex 
D6002 
4B02Hex
Type = 4BHex 
MAC ID = 02Hex 
D6003 
2021Hex
High byte of index = 20Hex
Low byte of index = 21Hex
D6004 
0004Hex
Reserved 
Sub index = 04Hex 
SDO response 
message 
editing area 
D6005 
0100Hex
Datum 1= 01Hex 
Datum 0 = 00Hex 
 
0100Hex in D6005 refers to the actual output frequency of the AC motor drive is 2.56Hz.   
z PLC 
program 
M1002
ZRST
D6250
D6281
ZRST
D6000
D6031
Reset response message editing area
and request message editing area.