Specifications 
Voltage Class 
230V Class 
Model Number VFD-_ _ _F23_ 
007
015
022
037
055
075 110 150
185
220
300
370
Max. Applicable Motor Output (kW) 
0.75
1.5 2.2 3.7 5.5
7.5  11  15 18.5
22  30  37 
Max. Applicable Motor Output (HP) 
1.0 2.0 3.0 5.0 7.5
10 15 20 25 30 40 50 
Rated Output Capacity (KVA)   
1.9 
2.5 4.2 6.5 9.5
12.5 18.3 24.7
28.6
34.3
45.7
55 
Rated Output Current (A) 
5.0 
7.0 11 17 25 33 49 65 75 90 120
145
Maximum Output Voltage (V) 
Proportional to Input Voltage 
Rated Frequency (Hz) 
0.10-120.00Hz 
O
u
tput Ratin
g
 
Carrier Frequency (kHz) 
4-10 3-9 
2-6 
Rated Input Current (A) 
5.7 7.6 
15.5
20.6
26 34 50 60 75 90 110
142
Rated Voltage 
3-phase 180-264 V 
Input
 
Ra
tin
Frequency Tolerance 
47 – 63 Hz 
 
Voltage Class 
460V Class 
Model Number VFD-_ _ _F43_ 
007 015 022 037 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600 1850 2200
Max. Applicable Motor Output (kW) 
0.75 1.5 2.2 3.7 5.5 7.5
11
15 18.5 22
30 37 45 55
75
90
110
132 160 185 220
Max. Applicable Motor Output (HP) 
1.0 2.0 3.0 5.0 7.5
10
15
20
25
30
40 50 60 75 100 125 150
175 215 250 300
Rated Output Capacity (KVA) 
2.3 3.2 4.2 6.5 10
14
18
25
29
34
46 56 69 84 114 137 168
198 236 281 350
Rated Output Current (A) 
2.7 4.2 5.5 8.5 13
18
24
32
38
45
60 73 91 110 150 180 220
260 310 370 460
Maximum Output Voltage (V) 
Proportional to Input Voltage 
Rated Frequency (Hz) 
0.10-120.00Hz 
O
u
tput Rating
 
Carrier Frequency (kHz) 
4-10 3-9 
2-6 
Rated Input Current (A) 
3.2 4.3 5.9 11.2 14
19
25
32
39
49
60 73 91 120 160 160 200
240 300 380 400
Rated Voltage 
3-phase    342-528 V 
Inpu
Rat
in
Frequency Tolerance 
47 – 63 Hz 
 
General Specifications 
Control System 
SPWM (Sinusoidal Pulse Width Modulation, carrier frequency 2-10kHz) 
Output Frequency Resolution 
0.01Hz 
Torque Characteristics 
Including the auto-torque, auto-slip compensation; starting torque can be 150% at 1.0Hz
Overload Endurance 
120% of rated current for 1 minute 
Accel/Decel Time 
1-36000/0.1-3600.0/0.01-360.00 seconds (3 Independent settings for Accel/Decel Time)
V/f Pattern 
Adjustable V/f pattern   
Cont
ro
l Ch
ar
ac
te
ri
st
ics 
Stall Prevention Level 
  20 to 150%, Setting of Rated Current 
Keypad 
Setting by 
 
Frequency 
Setting 
External Signal 
1 set of AVI analog voltage DC0-+10V/0-+5V, 2 sets of ACI analog current 0/4-20mA,
15 Multi-Function Inputs, RS-485 interface (MODBUS), External terminals UP/DOWN 
Key 
Keypad 
Set by RUN, STOP and JOG 
Operation 
Setting 
Signal 
External Signal 
Operation by FWD, REV, JOG and communication operation 
Multi-Function Input Signal 
Multi-step selection 0 to 15, Jog, accel/decel inhibit, first to forth accel/decel switches, 
counter, external Base Block (NC, NO), JOG, auxiliary motor start/maintenance 
Multi-Function Output 
Indication 
AC Drive Operating, Frequency Attained, Desired Frequency Attained, Zero speed, Base 
Block, Fault Indication, Local/Remote indication, and Auxiliary Motor Output 
Op
er
at
in
g Cha
ract
er
ist
ics 
Analog Output Signal 
2 sets of Analog frequency/current signal output