Specifications
Voltage Class
230V Class
Model Number VFD-_ _ _F23_
007
015
022
037
055
075 110 150
185
220
300
370
Max. Applicable Motor Output (kW)
0.75
1.5 2.2 3.7 5.5
7.5 11 15 18.5
22 30 37
Max. Applicable Motor Output (HP)
1.0 2.0 3.0 5.0 7.5
10 15 20 25 30 40 50
Rated Output Capacity (KVA)
1.9
2.5 4.2 6.5 9.5
12.5 18.3 24.7
28.6
34.3
45.7
55
Rated Output Current (A)
5.0
7.0 11 17 25 33 49 65 75 90 120
145
Maximum Output Voltage (V)
Proportional to Input Voltage
Rated Frequency (Hz)
0.10-120.00Hz
O
u
tput Ratin
g
Carrier Frequency (kHz)
4-10 3-9
2-6
Rated Input Current (A)
5.7 7.6
15.5
20.6
26 34 50 60 75 90 110
142
Rated Voltage
3-phase 180-264 V
Input
Ra
tin
g
Frequency Tolerance
47 – 63 Hz
Voltage Class
460V Class
Model Number VFD-_ _ _F43_
007 015 022 037 055 075 110 150 185 220 300 370 450 550 750 900 1100 1320 1600 1850 2200
Max. Applicable Motor Output (kW)
0.75 1.5 2.2 3.7 5.5 7.5
11
15 18.5 22
30 37 45 55
75
90
110
132 160 185 220
Max. Applicable Motor Output (HP)
1.0 2.0 3.0 5.0 7.5
10
15
20
25
30
40 50 60 75 100 125 150
175 215 250 300
Rated Output Capacity (KVA)
2.3 3.2 4.2 6.5 10
14
18
25
29
34
46 56 69 84 114 137 168
198 236 281 350
Rated Output Current (A)
2.7 4.2 5.5 8.5 13
18
24
32
38
45
60 73 91 110 150 180 220
260 310 370 460
Maximum Output Voltage (V)
Proportional to Input Voltage
Rated Frequency (Hz)
0.10-120.00Hz
O
u
tput Rating
Carrier Frequency (kHz)
4-10 3-9
2-6
Rated Input Current (A)
3.2 4.3 5.9 11.2 14
19
25
32
39
49
60 73 91 120 160 160 200
240 300 380 400
Rated Voltage
3-phase 342-528 V
Inpu
t
Rat
in
g
Frequency Tolerance
47 – 63 Hz
General Specifications
Control System
SPWM (Sinusoidal Pulse Width Modulation, carrier frequency 2-10kHz)
Output Frequency Resolution
0.01Hz
Torque Characteristics
Including the auto-torque, auto-slip compensation; starting torque can be 150% at 1.0Hz
Overload Endurance
120% of rated current for 1 minute
Accel/Decel Time
1-36000/0.1-3600.0/0.01-360.00 seconds (3 Independent settings for Accel/Decel Time)
V/f Pattern
Adjustable V/f pattern
Cont
ro
l Ch
ar
ac
te
ri
st
ics
Stall Prevention Level
20 to 150%, Setting of Rated Current
Keypad
Setting by
Frequency
Setting
Setting
External Signal
1 set of AVI analog voltage DC0-+10V/0-+5V, 2 sets of ACI analog current 0/4-20mA,
15 Multi-Function Inputs, RS-485 interface (MODBUS), External terminals UP/DOWN
Key
Keypad
Set by RUN, STOP and JOG
Operation
Setting
Signal
Setting
Signal
External Signal
Operation by FWD, REV, JOG and communication operation
Multi-Function Input Signal
Multi-step selection 0 to 15, Jog, accel/decel inhibit, first to forth accel/decel switches,
counter, external Base Block (NC, NO), JOG, auxiliary motor start/maintenance
Multi-Function Output
Indication
Indication
AC Drive Operating, Frequency Attained, Desired Frequency Attained, Zero speed, Base
Block, Fault Indication, Local/Remote indication, and Auxiliary Motor Output
Op
er
at
in
g Cha
ract
er
ist
ics
Analog Output Signal
2 sets of Analog frequency/current signal output