Warning 
  This instruction sheet only provides descriptions for electrical specifications, general specifications, installation and 
wiring. 
  This is an OPEN TYPE Controller. The DVPPF01-S should be kept in an enclosure away from airborne dust, humidity, 
electric shock risk and vibration. Also, it is equipped with protective methods such as some special tool or key to open 
the enclosure, so as to avoid the hazard to users or any damage to the module. DO NOT touch terminals when power 
on.
 
 
Introduction 
 Functions 
•  Cyclical data exchange process 
•  Support the SYNC and FREEZE for data synchronization between master and slaves 
•  Support Auto Baud rate detection 
•  Support 12MHz baud rate in DP network 
•  Cyclical data size is fixed to 4 bytes input and 4 bytes output 
•  Support GSD file configures by using configuration tools 
 Product Profile 
3
5
4
1
2
4
8
6
7
6
D
V
P
-P
F
0
1
x16
x16
 
 Model name 
 Extension port 
 Power/NET LED 
 Extension hole for mounting unit or module 
 DIN rail clip 
 Extension clip 
 Address switch 
 Profibus connector 
 
 Specifications 
 DP Connection 
Interface 
DB9 pin connector 
Transfer method 
High speed RS-485 
Transfer cable 
2-wire twisted shielded cable 
Electrical  isolation 
500V DC 
ENGLISH 
 Communication 
Message types 
DPV0, cyclical data exchange process 
Device ID 
09B9 HEX 
GSD file 
EATN09B9.GSD 
Model name 
DVPPF01-S 
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps 
Baud rates 
(auto  detected) 
1.5Mbps, 3Mbps, 6Mbps, 12Mbps 
 Environmental Specification 
Noise immunity 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
Environment 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2 
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Vibration/shock 
resistance 
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)   
IEC 61131-2 & IEC 68-2-27 (TEST Ea) 
Approvals 
 
   
 
Installation & Configuration    
 Dimensions 
 
     
D
V
P
-P
F
0
1
x16
x16
NET
POWER
1
0
 
Dimensions are in millimeter and [inch] 
 Installing the DVPPF01-S with the PLC Controller 
Open the extension cover with a screwdriver. 
Use a screwdriver to lift and unfasten the fixing clip. 
 
 
Connect the DVPPF01-S to extension port of PLC 
controller and fasten the fixing clip. 
Plug the Profibus connector to the socket of 
DVPPF01-S, and tighten screw to secure the 
connector. 
0
1
STO P
D
V
P
-1
2
S
A
RUN
RUN
BAT.LOW
ERROR
POWER
R
S
-2
3
2
R
S
-4
8
5
POWER
C0
X7
Y0
C1
Y1
Y2
Y3
C2
D
V
P
-P
F
0
1
s
X1
X2
X0
X5
X4
X3
X6
s
NET
x16
x16
1
0
 
 
 Cable Length and Baud Rate 
The Maximum cable length in a segment depends on the transmission speed. Profibus-DP communicates at 
speeds from 9.6kbps to 12Mbps over distances from 100 to 1,200 meters. 
Baud rate (bps) 
9.6k 
19.2k 
93.75k 
187.5k 
500k 
1.5M 
3M 
6M 
12M 
Length (m) 
1,200 
1,200 
1,200 
1,000 
400 
200 
100 
100 
100 
Check the extension I/O by WPL software: 
Connect to PLC MPU 
 
 
Once connection is successful, software will check if 32 
inputs/outputs is detected 
 
 PIN Definition of DP Connector 
PIN 
Definition 
Content 
PIN 
Definition 
Content 
-- 
N/C 
VP 
Positive  voltage 
-- 
N/C 
-- 
N/C 
RxD/TxD-P 
Data  receiving/sending 
P (B) 
RxD/TxD-N 
Data  receiving/sending 
N (A) 
-- 
N/C 
-- 
N/C 
DGND 
Data  reference 
potential  (C) 
 
 
 
1
5
9
6
 MAC ID Setting 
Address 
Content 
1…0x7D 
Valid Profibus address 
0 or   
0x7E…0xFF 
Invalid Profibus address. NET LED will rapidly blink with RED when 
node address is at 0, 0x7E…0xFF 
'
x16
'
x16
 
 Setting of DVPPF01-S Connect to Profibus-DP 
Connection example: 
DVP-PF01
Profibus network
DVP-PS01
DVP-12SA
D
V
P
-P
F
0
1
Y3
D
V
P
-1
2
S
A
0
1
R
S
-2
3
2
R
S
-4
8
5
X4
R UN
STO P
C1
Y1
C 2
Y2
X5
X6
Y0
C0
X7
RUN
POWER
BAT .LOW
ERROR
X2
X 1
X0
s
s
X3
x16
x16
N ET
P OWER
PC Master
1
0
 
DVPPF01-S provides fixed 4 bytes input data and 4 bytes output data to user in Profibus-DP system. 4 bytes 
input data are transmitted from DVPPF01-S module to Profibus-DP Master, it are mapping to Y20-Y57 in PLC 
controller when DVPPF01-S is the first extension unit of PLC. 4 bytes output data are transmitted from 
Profibus-DP Master, and it are also mapping to X20-X57 in PLC controller. 
 
 Data Mapping 
 
Following is a ladder program example: 
M1000
MOV
K4X20
D10
MOV
MOV
MOV
K4X40
D20
D21
K4Y40
K4Y20
D11
 
This program example copies the 4 bytes data from X20-X57 that transmitted by DP master to D10 and D11 
registers in PLC controller. And, PLC controller will write 4 bytes data in D20 and D21 registers to Y20-Y57, 
these 4 bytes data will send to DVPPF01-S, and DVPPF01-S will send these data to DP master. 
 
Troubleshooting
 
 NET LED 
LED status 
Indication 
Corrective actions 
OFF 
No power supply 
Verify DVPPF01-S is powered on 
Red blinking 
(rapidly) 
Invalid Profibus address setting 
via switch 
Check whether the switch setting is valid 
 
Setting range of slave: 1-125 
Set the valid value and re-power 
Red blinking 
Communication link to 
PROFIBUS, and no cyclical 
data  exchanged 
-- 
Red ON 
No connection to Profibus 
Verify that DP network installation is OK 
Verify that PLC is working 
Verify that switch address setting match with configuration in 
DP master 
Green 
blinking 
Reserved 
-- 
Green ON 
Cyclic data exchange in 
progress and OK 
-- 
 Power LED 
LED status 
Indication 
Corrective actions 
Green ON 
Power on 
-- 
OFF 
No power 
Verify that PLC controller is powered on 
 
注意事項 
  此安裝手冊只提供電氣規格、一般規格、安裝及配線等。 
  本機為開放型  (Open Type)  機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊意
外之外殼配線箱內。另必須具備保護措施  (如:特殊之工具或鑰匙才可打開)  防止非維護人員操作或意外衝擊
本體,造成危險及損壞。請勿在上電時觸摸任何端子。 
 
產品簡介 
 
    功能說明    
•  循環資料處理 
•  支援 SYNC 及 FREEZE 主站和從站間資料同步化 
•  支援自動偵測鮑率 
•  在 DP 網路中可使用 12MHz 鮑率 
•  循環資料處理固定為 4 bytes 和 4 bytes 輸出 
•  可使用設定工具設定 GSD file 
  各部介紹 
3
5
4
1
2
4
8
6
7
6
D
V
P
-P
F
0
1
x16
x16
 
 
機種名稱 
 
擴充機/擴充模組連接口 
 
電源、NET 指示燈 
 
擴充機/擴充模組定位孔 
 
DIN
軌固定扣 
 
擴充機/擴充模組固定扣 
 
位址旋鈕 
 
Profibus
連接口 
 
 
規格 
DP
連線 
介面 
DB9
接頭 
傳輸方式 
高速的 RS-485 
傳輸線 
2
絞線式隔離線 
電氣隔離 
500V DC 
 
 
繁體中文 
通訊 
訊息類型 
DPV0, 
循環式處理資料交換 
裝置 ID 
09B9 HEX 
GSD
檔案 
DELT09B9.GSD 
模組名稱 
DVP-PF01 
9.6kbps, 19.2kbps, 93.75kbps, 187.5kbps, 500kbps 
鮑率(自動偵測) 
1.5Mbps, 3Mbps, 6Mbps, 12Mbps 
環境規格 
雜訊免疫力 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV 
Analog & Communication I/O: 1KV 
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV 
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m 
操作/儲存環境 
操作:0°C ~ 55°C(溫度),50 ~ 95%(濕度),污染等級  2 
儲存:-25°C ~ 70°C(溫度),5 ~ 95%(濕度) 
耐振動/衝擊 
國際標準規範  IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) 
標準 
IEC 61131-2, UL 508 
標準 
 
安裝與設定 
  外觀圖 
 
 
 
D
V
P
-P
F
0
1
x16
x16
NET
POWER
1
0
 
單位: mm [inches]