Please read this instruction carefully before use.
 
3
 
DOP series Extension Digital I/O Module should be used with DOP-AE series HMI product. Ensure to 
switch off the power before wiring. 
3
 
Please install this DOP series Extension Digital I/O Module in an enclosure free of airborne dust, 
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from 
operating the device (e.g. key or specific tools are required for opening the enclosure) in case danger 
and damage on the device may occur. 
3
 
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may 
occur. Check all the wiring again before switching on the power. 
3
 
DO NOT touch any internal circuit in 1 minute after the power is switched off. Do NOT touch any 
terminal when the power is switched on.   
3
 
Make sure the ground terminal 
  is correctly grounded in order to prevent electromagnetic 
interference. 
3
 
DO NOT place any heavy objects on the connection port of DOP series Extension Digital I/O Module. 
Doing so may damage the product. 
X
 
Introduction
 
1.1 Model 
Explanation 
 
DOP -  EXIO 
14 
AE 
(1)   (2) 
(3) 
(4)  (5) 
 
(1) Product Name   
DOP: Delta Operation Panel 
(2) Series 
EXIO: Extension Digital I/O 
(3) Input / Output Point 
14: 8 input points / 6 output points 
28: 16 input points / 12 output points 
(4) Output Contact Type 
R: Relay 
(5) Applicable HMI Series 
AE: DOP-AE Series HMI 
 
1.2 Product 
Outline 
 
1. Connection Port 
2. Direct Mounting Hole 
3. Input / Output Terminals 
4. Nameplate 
 
1.3 Model 
Name 
Input / Output 
Input Unit 
Output Unit 
Model Name 
Power 
Point 
Type 
Point 
Type 
DOP-EXIO14RAE 8 
Relay 
DOP-EXIO28RAE 
5VDC, 
supplied 
by HMI 
16 
DC Type 
Sink or 
Source 
12 Relay 
Y
 
Function Specifications
 
Item 
Specifications 
Remark 
Control Method 
Stored program, cyclic scan system 
I/O Processing Method 
Batch I/O (refresh) 
Immediate refresh command available 
only with I/O of the MPU 
Execution Speed 
Basic command (average approx. 30 
us) 
Application command (30 ~ hundreds 
us) 
Program Language 
Commands + Ladder Diagram + 
SFC 
Step commands included 
Item 
Specifications 
Remark 
Program Capacity 
999 Steps 
Built-in EEPROM 
Commands 
Basic commands: 32 (including the 
STL commands) 
Application commands: 59 
Step Relay 
(Latched) 
General 
Step Point
128 Points 
S10 ~ S127 
General 
1280 Points 
M0 ~ M511, M768 ~ M999, 744 points; 
M1000 ~ M1279, 280 points
*1
 
Auxiliary 
Relay 
Latched 
256 Points 
M512 ~ M767 
64 Points 
T0~T63 (100 ms time base) 
63 Points 
T64~T126 (10 ms time base) 
Timer Digital 
1 Points 
T127 (1 ms time base) 
General 
112 Points 
C0 ~ C111 
Latched 
16 Points 
C112 ~ C127 
Counter 
32bit 
13 Points 
C235,C236,C237,C238,C241,C242, 
C244,C246,C247,C249,C251,C252, 
C254 (all of them are latched type) 
General 
408 Points 
D0 ~ D407 
Data Register 
Latched 
192 Points 
D408 ~ D599 
Pointer 
64 Points 
P0 ~ P63 
Index 
Register 
E / F 
E, F 
Decimal K 
16bit: -32768 ~ +32767 
32bit: -2147483648 ~ +2147483647 
Constant 
Hexadecim
al H 
16bit: 0000 ~ FFFF 
32bit: 00000000 ~ FFFFFFFF 
Self Diagnosis / Protection 
I/O check, system execution timeout check, invalid command check, program 
check and password settings 
Monitor / Debug 
Program execution time display, bit / word, device settings 
*1: M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the special auxiliary relays (special M). 
Z
 
Electrical Specifications
 
Item / Model Name 
DOP-EXIO14RAE 
DOP-EXIO28RAE 
Power Supply Voltage 
5VDC, 1A (supplied by HMI) 
Power Consumption 
0.25W 
0.5W 
Noise Immunity 
RS:   Frequency: 80MHz ~ 1GHz, 1.4GHz ~ 2.0GHz, Test level 10V/m 
CS: Frequency: 0.15MHz ~ 80MHz, Test level 10V (HMI power port & I/O line) 
ESD: Air discharge  ±8KV 
EFT:  ±1.5KV (HMI power port) 
±
1KV (I/O line) 
Surge:  ±2KV (HMI power port) 
Ambient Temperature / 
Humidity  
Operation: 0°C ~ 50°C (Temperature), 10 ~ 90% (Humidity), 
Storage: -40°C ~ 85°C (Temperature), 10 ~ 90% (Humidity) 
Vibration / Shock 
IEC 61131-2 Compliant 
5Hz≦f<9Hz = Continuous: 1.75mm / Occasional: 3.5mm   
9Hz≦f≦150Hz = Continuous: 0.5g / Occasional: 1.0g 
  X, Y, Z directions for 10 times 
Weight 
Approx. 95.5g 
Approx. 116g 
 
Input Point Electric Specifications 
Input Type 
DC (SINK or SOURCE) 
Input Voltage 
24VDC (5mA) 
Off→On, above 16VDC 
Active Level 
On→Off, below 14.4VDC 
Response Time 
Approx. 10ms 
 
Output Point Electric Specifications 
Output Type 
Relay-R 
Current Specifications 
1.5A / 1 Point (5A/COM) 
Voltage Specifications 
250VAC, below 30VDC 
75VA (Inductive)   
Maximum Loading 
90 W (Resistive) 
Response Time 
Approx. 10 ms 
Mechanical Life 
2 × 10
7
 times (without load) 
Electrical Life 
100,000 times (3A 250VAC/30VDC) 
6,000 times (5A 250VAC/30VDC) 
[
 
Installation & Wiring
 
4.1 Wiring 
22-16AWG
< 1.5mm
 
1.  Please use the 28-16 AWG (1.5mm
2
) single-core bare wire (Solid type) or 
the multi-core wire (Stranded type) for the I/O wiring. The stripped length of 
the wire should be 6-7mm, and the torque specification of the screw for the 
terminal is 4.5lb-in. Please refer to the specifications of the terminal
 
shown 
in the figure on the left. 
2.  DO NOT place the I/O signal wires and power supply wire in the same 
wiring duct. 
4.2 Caution 
™ 
Environment 
1. DO NOT install the Extension Digital I/O Module in a place subjected to corrosive or flammable gases, 
liquids, or airborne dust or metallic particles. 
2. DO NOT install the Extension Digital I/O Module in a location high temperature and high humidity (where 
temperature and humidity will exceed specification). 
3. DO NOT install the Extension Digital I/O Module in a location where vibration and shock will exceed 
specification.  
™ 
Wiring Note 
1. Please avoid any conductive debris and tiny metal materials enter the Extension Digital I/O Module when 
screwing and wiring. 
2. Allow a minimum space of 50mm between the Extension Digital I/O Module and other control devices, and 
keep the Extension Digital I/O Module away from the high-voltage lines or any power equipment.   
4.3 Terminal 
Identification 
 
4.4 Wiring 
™
 There are two types of DC inputs, SINK and SOURCE, and they are defined as follows: 
Sink = (common port for current input S/S) 
Source = (common port for current output S/S) 
 
 
™ 
Input Point Wiring
 (S/S shown in the wiring diagrams indicates SS1 or SS2 contact)
 
DC Signal IN 
Input point loop equivalent circuit 
Wiring loop 
SINK mode 
 
 
DC Signal IN 
Input point loop equivalent circuit 
Wiring loop 
SOURCE mode 
 
™ 
Output Point Wiring 
Be careful with the connection of the common terminals 
when wiring outputs. For example, when wiring 
DOP-EXIO14RAE (DOP-EXIO28RAE), output terminal 
Y0 (Y10) uses C0 (C10), Y1 (Y11) uses C1 (C11), Y2 ~ 
Y3 (Y12 ~ Y13) uses C3 (C13), Y4 ~ Y5 (Y14 ~ Y15) 
uses C5 (C15), as shown below: 
NOTE
 
1)  The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download the most 
updated version at http://www.delta.com.tw/industrialautomation.  
http://www.delta.com.tw/industrialautomation/
 
 
Extension Digital I/O Module 
Instruction Sheet 
 