LST M512ME Fascicule

Page de 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
M512ME_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The  addressable  Conventional  Zone  Module  M512ME 
serves  for  the  integration  of  conventional  detectors, 
 detectors for intrinsically safe areas and special detec-
tors into an ADM loop with System Sensor/200 proto-
col. The conventional zone module provides an output 
for resetting special detectors.
The address of the module is easily selected by means 
of two integrated decadic rotary switches. The Surface 
Mounting  Box  SMB500  is  required  for  mounting  the 
module.
The module must be powered by an external supply.
•   ADM loop technology with
System Sensor/200 protocol
•   Integration of conventional and 
special detectors into the ADM loop
•  Output for resetting of detectors
•   Setting of module address via 
decadic rotary switches
Specifi cations
Operating voltage 
18 – 32VDC
Current consumption from loop 
300µA (quiescent)
Ambient temperature 
-10°C to +60°C
Dimensions L × W × H (without mounting plate) 
70 × 70 × 32 (mm)
Weight 
142g
Approval 
VdS G297009
Order number 
249045
Order name 
Conventional Zone Module/Anal./500/SS M512ME
Surface Mounting Box
Dimensions W × H × D 
125 × 124 × 55 (mm)
Colour 
cream
Weight 
155g
Order number  
249004
Order name 
Surface Mounting Box for M500/SS SMB500