Emerson CW Manuel D’Utilisation

Page de 28
Blower Duct & Deck Dimensions, CW106 and CW114, Upflow Models
12
6.0
B
LOWER
 D
UCT
 & D
ECK
 D
IMENSIONS
, CW106 
AND
 CW114, U
PFLOW
 M
ODELS
Model
Blower
Supply
Motor,
hp
Dimensional Data, inches (mm)
 Net Weight
lb. (Kg)
A
B
C
D
E
F
CW106
15 x 15
Top Front
10-15
27-1/2
(699)
3 1/2
(89)
18-11/16
(475)
16-3/16
(411)
10
(254)
4 1/2
(114)
1785
(810)
Top Rear
10-15
27-1/2
(699)
12 5/16
(313)
18 11/16
(475)
16 3/16
(411)
10
(254)
4 1/2
(114)
CW114
 15 x 11
Top Front
10-15
30
(762)
3 1/2
(89)
14 3/4
(375)
16 3/16
(411)
10
(254)
4 1/2
(114)
1925
(873)
20
30
(762)
3 1/2
(89)
14 3/4
(375)
16 3/16
(411)
10
(254)
4 1/2
(114)
Top Rear
10-20
30
(762)
12 5/16
(313)
14 3/4
(375)
16 3/16
(411)
10
(254)
4 1/2
(114)
76" 
Ref
F
Blower Deck
Front or Rear Air Supply
Top of Unit
DPN001663
Rev. 0
C
C
C
E
E
D
35"
Ref
B
Duct Flanges on Three Blowers
122" Ref
A
Front of Unit
Blower Duct Flange Location
2
1
*Follow standard practices on all duct work.
1. Straight section of duct off of unit to be 1.5 
to 2.5 times the longest blower dimension.
2. Typical ducting shown, may run to either 
side.
TOP-FRONT
SUPPLY SHOWN
1" (25.4mm) Flange 
for Decorative
Plenum Alignment
Filter
Access
(both
ends)
Flanges Provided on 
Blower Outlets for 
Supply Air Ducting
24-1/4" (616mm)
117-1/2"
(2985mm)
2-1/4"
(57mm)
22"
(546mm)
Air 
Return 
Opening
4"
(102mm)
NOTE: Only 120" 
Upflow has rear 
return filter box.