Emerson CW Manuel D’Utilisation

Page de 28
Electrical Data—Units with EC Fans
5
3.0
E
LECTRICAL
 D
ATA
—U
NITS
 
WITH
 EC F
ANS
3.1
CW106 and CW114 Electrical Data with EC Fans
3.2
CW181 Electrical Data with EC Fans
Table 1
Electrical data—60Hz-3 phase
Reheat
Humidifier
Volts
FLA
WSA
OPD
Electric
Infrared
460
65.4
81.8
90
Electric
Infrared
575
53.4
66.8
70
Electric
Infrared
460
53.8
67.3
70
Electric
Infrared
575
41.8
52.3
60
None
Infrared
460
26.3
32.9
35
None
Infrared
575
23.3
29.1
30
None
None
460
14.7
15.9
20
None
None
575
11.7
12.7
15
Table 2
Electrical data—50Hz-3 phase
Reheat
Humidifier
Volts
FLA
WSA
Electric
Electric
400
70.8
88.5
Electric
None
400
58
72.5
None
Electric
400
27.5
34.4
None
None
400
14.7
15.9
Table 3
CW181 electrical data—60Hz-3 phase
Reheat
Humidifier
Volts
FLA
WSA
OPD
Electric
Infrared
460
69
86.3
90
Electric
Infrared
575
56.4
70.5
80
Electric
None
460
57.4
71.8
80
Electric
None
575
44.8
56
60
None
Infrared
460
29.9
37.4
35
None
Infrared
575
26.3
32.9
35
None
None
460
18.3
19.8
25
None
None
575
14.7
15.9
20
Table 4
CW181 electrical data—50Hz-3 phase
Reheat
Humidifier
Volts
FLA
WSA
Electric
Electric
400
74.4
93
Electric
None
400
61.6
77
None
Electric
400
31.1
38.9
None
None
400
18.3
19.8