Emerson 00825-0100-4075 Manuel D’Utilisation

Page de 28
Quick Installation Guide
00825-0100-4075, Rev BA
February 2010
Smart Wireless THUM Adapter
3
W
IRELESS
 C
ONSIDERATIONS
Power Up Sequence
Power should not be applied to any wireless device until the Smart Wireless Gateway 
(“Gateway”) is installed and functioning properly. Wireless devices should also be powered 
up in order of proximity from the Gateway, beginning with the closest. This will result in a 
simpler and faster network installation. Enable Active Advertising on the Gateway to ensure 
that new devices join the network faster. For more information see the Smart Wireless 
Gateway Manual (Doc. No. 00809-0200-4420).
THUM Adapter Position
If possible, the THUM Adapter should be positioned vertically, either straight up or straight 
down, and it should be approximately 3 ft. (1 m) from any large structure, building, or 
conductive surface to allow for clear communication to other devices. If the THUM Adapter 
is mounted horizontally wireless communication range may be decreased. See THUM 
Adapter reference manual (00809-0100-4075) for more information.
Figure 1.  THUM Adapter Position
Conduit Entry
When installing the THUM Adapter into the conduit entry of a wired device, use an approved 
thread sealant. Thread sealant provides a water tight seal. The thread sealant also provides 
lubrication to ensure easy removal of the THUM Adapter.
M20 Conduit Adapter
When using the M20 Conduit Adapter on the THUM Adapter, use an approved thread 
sealant and tighten wrench tight to the THUM Adapter.
Field Communicator Connections
In order for the Field Communicator to interface with the THUM Adapter, the wired device 
must be powered. The Field Communicator must be put into poll mode and should use the 
THUM Adapter address of 63. 
4075_QIG_Rev_BA.fm  Page 3  Friday, February 19, 2010  11:08 AM