Emerson SiteLink-2E Manuel D’Utilisation

Page de 4
4
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject 
to change without notice.
® Liebert and the Liebert logo are registered trademarks of 
Liebert Corporation. All names referred to are trademarks or 
registered trademarks of their respective owners.
SL-27218_REV0_01-07
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
Specifications
Wiring Specifications
Ordering Information
Power
24VAC ±10%, 50 to 60Hz, 24VA, or 26VDC ±10%, 10W, 48VDC
Dimensions
W x D x H: in. (mm)
Module: 11.3 x 0.56 x 7.5 (287 x 14.2 x 190.5)
Enclosure (brushed aluminum): 14.25 x 2.85 x 12 (362 x 72.4 x 304.8)
Communication Ports
• Ethernet Port
10/100Base-T Fast Ethernet port.
• ARC156 Port
ARCNET156 or EIA-485 communication. In ARCNET156 mode, the port communicates via
BACnet ARC156.
• TPI Port S1
EIA-232/422/485 configurable port for interaction with 3rd-party building automation systems
via software-selectable protocols. May also be configured for remote modem access.
• EIA-422/485
Ports 1-12 - for
communication with
equipment via
software-selectable
protocols & baud
rates
Each port can  be individually set for different protocols & baud rates.
The number of ports varies by model:
SiteLink-2E (SSW-2E)
SiteLink-4E (SSW-4E)
SiteLink-12E (SSW-12E)
• Ports 11-12 
These two ports include
an option for EIA-232
connection.
• Ports 9-12 
These four ports include
an option for EIA-232
connection.
• Ports 1-12 
Four of these 12 ports (9-12)
include an option for EIA-232
connection.
Environmental 
Operating Range
20°F to 140°F (-29°C to 60°C); 10 to 90% relative humidity, non-condensing
Note: Control modules should be installed within the building.
Memory
16 MByte non-volatile battery-backed SDRAM and 8 MByte Flash
Protection
Built-in surge and transient protection circuitry - internal solid state polyswitches on incoming
power and network communications connections
Battery
3V lithium battery P/N CR-123A; battery shelf life is 10 years with 720 hours of continuous operation
Fault Detection
Hardware watchdog timer
Agency Listings
UL, cUL, CE, FCC
Connection
 Supported Wire Types
 Maximum Wire Length
 Rating
Ethernet 10 BaseT
CAT 5
 328 ft. (100m)
 N/A
BACnet Port
MAGNUM Cable P/N A3-ARC-156-2
 3000 ft. (915m)
 N/A
Port S1 EIA-485
18-22 AWG Stranded & Shielded; 18 AWG (recommended)
Non Plenum - Belden 9461; Plenum - Belden 88761 
 1000 ft. (300m)
 N/A
Port S1 EIA-232
18-22 AWG Stranded & Shielded; 18 AWG (recommended)
Non Plenum - Belden 9461; Plenum - Belden 88761 
50 ft. (15m)
 N/A
Quantity
Part #
Description
SSW-12E
SiteLink-12E with enclosure - communicates with up to 12 Liebert unit controllers
SSW-12EWO
SiteLink-12E without enclosure - communicates with up to 12 Liebert unit controllers
SSW-4E
SiteLink-4E with enclosure - communicates with up to 4 Liebert unit controllers
SSW-4EWO
SiteLink-4E without enclosure - communicates with up to 4 Liebert unit controllers
SSW-2E
SiteLink-2E with enclosure - communicates with up to 2 Liebert unit controllers
SSW-2EWO
SiteLink-2E without enclosure - communicates with up to 2 Liebert unit controllers