Emerson ITR Manuel D’Utilisation

Page de 74
System Data
24
13.0 S
YSTEM
 D
ATA
Table 2
Liebert Challenger ITR air-cooled data—60 Hz
System Type
BR = Horizontal Flow
Self-Contained
Split Systems
w/Outdoor Prop-Fan
Condensing Unit
w/Indoor Centrifugal
Condensing Unit
Indoor Unit
BR 067A
BR 060E
BR 060E
Net Capacity Data
BTU/H
kW
BTU/H
kW
BTU/H
kW
100°F DB, 70°F WB (37.8°C DB, 21.1°C WB) 20% RH
Total
78,100
22.9
76,200
22.3
73,200
21.4
Sensible
78,100
22.9
76,200
22.3
73,200
21.4
Non Standard Flow Rates
2400 CFM
2300 CFM
2100 CFM
95°F DB, 68.3°F WB (35°C DB, 20.2°C WB) 24% RH
Total
77,500
22.7
75,800
22.2
73,000
21.4
Sensible
77,500
22.7
75,800
22.2
73,000
21.4
Non Standard Flow Rates
2700 CFM
2500 CFM
90°F DB, 66.5°F WB (32°C DB, 19.2°C WB) 28% RH
Total
73,600
21.6
72,400
21.2
70,600
20.7
Sensible
73,600
21.6
72,400
21.2
70,600
20.7
85°F DB, 64.4°F WB (29.4°C DB, 18
°
C WB) 32% RH
Total
69,700
20.4
68,400
20.0
66,800
19.6
Sensible
69,700
20.4
68,400
20.0
66,800
19.6
80°F DB, 62.7°F WB (26.7°C DB, 17.1°C WB) 38% RH
Total
66,000
19.3
64,400
18.9
63,100
18.5
Sensible
66,000
19.3
64,400
18.9
63,100
18.5
80°F DB, 66.5°F WB (26.7°C DB, 19.2°C WB) 50% RH
Total
66,900
19.6
65,300
19.1
63,800
18.7
Sensible
54,600
16.0
54,000
15.8
53,400
15.6
75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH
Total
62,700
18.4
60,800
17.8
59,600
17.5
Sensible
53,000
15.5
52,300
15.3
51,800
15.2
75°F DB, 61.1°F WB (23.9°C DB, 16.2°C WB) 45% RH
Total
61,200
17.9
60,700
17.8
59,600
17.5
Sensible
57,000
16.7
60,700
17.8
59,600
17.5
72°F DB, 60.1°F WB (22.2°C DB, 15.6°C WB) 50% RH
Total
60,200
17.6
58,200
17.1
57,200
16.8
Sensible
52,000
15.2
51,200
15.0
50,700
14.9
72°F DB, 58.7°F WB (22.2°C DB, 14.8°C WB) 45% RH
Total
58,900
17.3
58,400
17.1
57,500
16.8
Sensible
55,800
16.3
58,400
17.1
57,500
16.8
Fan Data (Blower A12x9AT)**
Standard Air, CFM (CMH)
2800 (4760)
2800 (4760)
2800 (4760)
Standard Fan Motor, hp (kW)
1-1/2 (1.1)
1-1/2 (1.1)
1-1/2 (1.1)
Opt Fan Motor, hp (kW)
2 (1.5)
2 (1.5)
2 (1.5)
Ext Static, in. WG (Pa)
.3 (75)
.3 (75)
.3 (75)
Evaporator Coil (V-FRAME, at standard conditions)
Face Area, ft.
2
 (m
2
)
6.67 (.62)
6.67 (.62)
6.67 (.62)
Rows
4
4
4
Face Velocity - FPM (m/s)
405 (2.1)
405 (2.1)
405 (2.1)
Electric Reheat 2 Stage (Stainless Steel, Fin Tubular) - Standard
Capacity, inc. motor heat, BTU/H (element kW)
56,200 (15)
56,200 (15)
56,200 (15)
Hot Water Reheat 180°F (82.2°C) EWT, 75°F (23.9°C) EAT - Optional (includes std air volume and opt fan motor hp)
Capacity, inc. motor heat, BTU/H (kW)
88,700 (26.0)
88,700 (26.0)
88,700 (26.0)
Flow Rate - GPM (l/s)
5.0 (.32)
5.0 (.32)
5.0 (.32)
Pressure drop - ft. (kPa)
16.9 (50.4)
16.9 (50.4)
16.9 (50.4)
* The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72°F (22.2°C) and 50% RH is the 
standard rating for ASHRAE 127-2001. All capacities are nominal values; actual performance will be ±5%.
** Data rated with 2" 20% ASHRAE filter. Some options or combinations of options may result in reduced airflow. Consult factory for 
recommendations.