FM-3 Programming Module Reference Manual
Tuning Procedure
Once the initial setup has been completed, you can run the system to determine if the level of 
tuning is adequate for the application. There are basically four levels of tuning for a drive.
No Tuning
Basic  Level
Intermediate Level
Fully Optimized Level
Each level is slightly more involved than the previous one requiring you to enter more 
information. If your system needs optimization, we recommend that you start with the Basic 
Level, then determine if further tuning is needed based on axis performance.
The setup procedures explained here assume that you are using PowerTools FM-3 software 
or an FM-P.
Initial settings
Set the drive tuning parameters as follows:
Inertia Ratio = 0
Friction = 0
Response = 50
High Performance Gains = Enabled
Feedforwards = Disabled
Tuning steps
If your Inertia Ratio is greater than 10 times the motor inertia go directly to the Intermediate 
Level tuning.
No Tuning
No tuning will be required in most applications where the load inertia is 10 times the motor 
inertia or less.
Basic Level
Adjust Response to obtain the best performance.
Intermediate Level
1.
Calculate or estimate the load inertia. It is always better to estimate low.
2.
Disable the drive.